| Plan Review Notes For Permit 10110288 |
| Permit Number |
10110288 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-30 17:04:14 | 525 OKEECHOBEE BOULEVARD, SUITE #750 | | | PERMIT #10110288 | | | REVIEW COMMENTS - FIRE | | | | | | THE 2007 EDITION OF THE FLORIDA FIRE PREVENTION CODE | | | USES THE 2006 EDITION OF THE LIFE SAFETY CODE - NFPA | | | 101 WITH FLORIDA AMENDMENTS. THE COVER SHEET REFERENCES | | | THE 2003 EDITION OF NFPA 101. | | | | | | THE CURRENT EXIT ACCESS CONFIGURATION CREATES A COMMON | | | PATH OF TRAVEL GREATER THAN 100 FEET. THE TWO DOORS | | | (701 & 714) FROM THE TENANT SUITE ARE STILL CONSIDERED | | | EXIT ACCESS AND NOT EXITS. OCCUPANTS EXITING THROUGH | | | DOOR 714 WILL CONVERGE WITH THE OCCUPANTS EXITING | | | THROUGH DOOR 701. | | | | | | PROVIDE PORTABLE FIRE EXTINGUISHER LOCATIONS ON THE | | | FLOOR PLAN. | | | | | | TO OBTAIN A BUILDING PERMIT, CONSTRUCTION DOCUMENTS ARE | | | NEEDED FOR THE MODIFICATION OF THE FIRE ALARM AND | | | AUTOMATIC SPRINKLER SYSTEMS. ADDITIONALLY, SEPARATE | | | PLANS AND PERMITS WILL BE NEEDED FOR THE FIRE ALARM AND | | | SPRINKLER SYSTEM SHOP DRAWINGS. | | | | | | THE COLUMNS AND FURNITURE LAYOUT CREATE AN AISLE THAT | | | IS LESS THAN 36 INCHES IN WIDTH ON SHEET A-1.1. | | | | | | THE ACCESS-CONTROLLED EGRESS SYSTEM SHALL BE INTEGRATED | | | WITH THE BUILDING FIRE ALARM AND FIRE SPRINKLER SYSTEM. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|