Date Text
2010-11-23 12:15:14550 OKEECHOBEE BOULEVARD, SUITE UP#23
 PERMIT #10110256
 REVIEW COMMENTS - FIRE
  
 DRAWINGS ID-1 AND ID-2 ARE NOT SCALABLE AT ONE-QUARTER
 INCH EQUALS ONE-FOOT.
  
 PLEASE CLARIFY THE TWO LOWER CEILING ARROWS POINTING TO
 DIFFERENT AREAS IN THE SAME ROOM ON DRAWING ID-2.
  
 PLEASE PROVIDE CEILING HEIGHTS, SOFFIT ELEVATIONS, AND
 LIGHT COVE DIMENSIONS.
  
 THE RELOCATION OF FIRE SPRINKLERS ON DRAWING ID-3
 RESULTS IN INADEQUATE COVERAGE PER NFPA 13.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR AUTOMATIC
 SPRINKLER SYSTEM MODIFICATIONS.
  
 NOTE: THE CURRENT DIMENSIONS AND LAYOUT OF THE NEW
 SOFFITS MAY PREVENT CODE COMPLIANT SPRINKLER COVERAGE.
 THE USE OF SIDEWALL SPRINKLERS IS GENERALLY LIMITED TO
 FLAT CEILINGS WITH LITTLE OR NO OBSTRUCTIONS (SOFFITS).
 THE SPRINKLERS NEED TO BE INSTALLED ACCORDING TO THEIR
 LISTING CRITERIA AND THE REQUIREMENTS OF NFPA 13.
 INSTALLATION EXAMPLES INCLUDE: SIDEWALL SPRINKLERS
 SHALL NOT PROJECT MORE THAN 6-INCHES FROM THE WALL ON
 WHICH THEY ARE MOUNTED; SIDEWALL SPRINKLERS SHALL BE
 INSTALLED NO CLOSER THAN 8-FEET FROM LIGHT FIXTURES OR
 SIMILAR OBSTRUCTIONS; WHERE SOFFITS EXCEED 8-INCHES IN
 WIDTH, PENDENT SPRINKLERS SHALL BE INSTALLED UNDER THE
 SOFFIT.
  
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730