| 2010-11-23 12:15:14 | 550 OKEECHOBEE BOULEVARD, SUITE UP#23 | | | PERMIT #10110256 | | | REVIEW COMMENTS - FIRE | | | | | | DRAWINGS ID-1 AND ID-2 ARE NOT SCALABLE AT ONE-QUARTER | | | INCH EQUALS ONE-FOOT. | | | | | | PLEASE CLARIFY THE TWO LOWER CEILING ARROWS POINTING TO | | | DIFFERENT AREAS IN THE SAME ROOM ON DRAWING ID-2. | | | | | | PLEASE PROVIDE CEILING HEIGHTS, SOFFIT ELEVATIONS, AND | | | LIGHT COVE DIMENSIONS. | | | | | | THE RELOCATION OF FIRE SPRINKLERS ON DRAWING ID-3 | | | RESULTS IN INADEQUATE COVERAGE PER NFPA 13. | | | | | | SEPARATE PLANS AND PERMIT REQUIRED FOR AUTOMATIC | | | SPRINKLER SYSTEM MODIFICATIONS. | | | | | | NOTE: THE CURRENT DIMENSIONS AND LAYOUT OF THE NEW | | | SOFFITS MAY PREVENT CODE COMPLIANT SPRINKLER COVERAGE. | | | THE USE OF SIDEWALL SPRINKLERS IS GENERALLY LIMITED TO | | | FLAT CEILINGS WITH LITTLE OR NO OBSTRUCTIONS (SOFFITS). | | | THE SPRINKLERS NEED TO BE INSTALLED ACCORDING TO THEIR | | | LISTING CRITERIA AND THE REQUIREMENTS OF NFPA 13. | | | INSTALLATION EXAMPLES INCLUDE: SIDEWALL SPRINKLERS | | | SHALL NOT PROJECT MORE THAN 6-INCHES FROM THE WALL ON | | | WHICH THEY ARE MOUNTED; SIDEWALL SPRINKLERS SHALL BE | | | INSTALLED NO CLOSER THAN 8-FEET FROM LIGHT FIXTURES OR | | | SIMILAR OBSTRUCTIONS; WHERE SOFFITS EXCEED 8-INCHES IN | | | WIDTH, PENDENT SPRINKLERS SHALL BE INSTALLED UNDER THE | | | SOFFIT. | | | | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|