2010-11-30 12:45:24****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A COMPLETE STRUCTURAL DETAIL SHOWING
 PROPOSED CONSTRUCTION, FBC106, FBC1607, FBC1013, FBC
 R312. FOR INSTANCE, DETAIL DOES NOT SHOW HEIGHT, PICKET
 SPACING, OR CONNECTORS OTHER THAN POST.
  
 2. PLANS ARE TO DECLARE OCCUPANCY CLASSIFICATION (FBC
 CH. 3) AND DESIGN CRITERIA FBC1607.7. CALCULATIONS MAY
 BE REQUIRED.
  
 3. PROVIDE A STRUCTURAL ENGINEER'S ANALYSIS OF THE
 EXISTING SUBSTRATE AND PROPOSED DESIGN IN ORDER TO SHOW
 THAT THE PROPOSED RAILING CAN MEET THE LOADS REQUIRED
 BY FBC1607, FBC R TABLE 301.5.
  
  
  