| Plan Review Notes For Permit 10110239 |
| Permit Number |
10110239 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-30 12:45:24 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PROVIDE A COMPLETE STRUCTURAL DETAIL SHOWING | | | PROPOSED CONSTRUCTION, FBC106, FBC1607, FBC1013, FBC | | | R312. FOR INSTANCE, DETAIL DOES NOT SHOW HEIGHT, PICKET | | | SPACING, OR CONNECTORS OTHER THAN POST. | | | | | | 2. PLANS ARE TO DECLARE OCCUPANCY CLASSIFICATION (FBC | | | CH. 3) AND DESIGN CRITERIA FBC1607.7. CALCULATIONS MAY | | | BE REQUIRED. | | | | | | 3. PROVIDE A STRUCTURAL ENGINEER'S ANALYSIS OF THE | | | EXISTING SUBSTRATE AND PROPOSED DESIGN IN ORDER TO SHOW | | | THAT THE PROPOSED RAILING CAN MEET THE LOADS REQUIRED | | | BY FBC1607, FBC R TABLE 301.5. | | | | | | | | | |
|