| Plan Review Notes For Permit 10110225 |
| Permit Number |
10110225 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-01 16:00:43 | DENIED BY ELECTRICAL | | | | | | 1) THE ELECTRICAL DIAGRAM SHOWS TWO PUMP MOTORS AND THE | | | PIPING DIAGRAM ONLY HAS ONE PUMP. PLEASE CLARIFY. | | | | | | 2) THE ELECTRICAL DIAGRAM SHOWS AN ELECTRIC HEAT PUMP | | | POOL HEATER. SUBMIT 2 COPIES OF THE SPECIFICATIONS FOR | | | THIS HEATER. | | | | | | 3) SPECIFY ON THE PLANS THAT A THERMAL COVER IS | | | REQUIRED FOR HEATED SWIMMING POOLS AND SPAS PER | | | 13-612.AB.2.3.2 OF THE 2007 FLORIDA ENERGY CODE. | | | | | | 4) SHOW COMPLIANCE WITH 13-612.AB.2.3.3 WHICH REQUIRES | | | TIME CLOCKS ON PRIVATE POOL PUMPS. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|