Plan Review Notes
Plan Review Notes For Permit 10110225
Permit Number 10110225
Review Stop B
Sequence Number 1
Notes
Date Text
2010-12-02 10:17:51DENIED BY BUILDING
  
 1) THE 8-1/2" X 11" SPA DRAWINGS FROM DOUGLAS W. BAUMAN
 P.E. ARE REQUIRED TO BE SIGNED AND SEALED PER FS 471.
  
 2) SHOW COMPLIANCE WITH FBC R301.2.1 THE POOL EQUIPMENT
 IS REQUIRED TO BE ANCHORED TO UPLIFT AND OVERTURNING IN
 A 140 MPH WIND SPEED.
  
 3) SHOW COMPLIANCE WITH FBC R4101.17 FOR SWIMMING POOL
 BARRIER REQUIREMENTS.
  
 4) THE VALVE FOR THE POOL AND SPA SPECIFIED ON THE
 APPLICATION IS TOO LOW. THE PERMIT VALUE IS BASED ON
 THE TOTAL COSTS INCLUDING ALL DESIGN COSTS, MATERIALS,
 LABOR, OVERHEAD AND PROFIT AS A CONTRACTOR WOULD CHARGE
 PER FBC 108.3. THE VALUE HAS BEEN CONSERVATIVELY
 INCREASED TO $ 15,000.00 BASED ON MARSHALL AND SWIFT
 PUBLISHED DATA.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]