| 2011-05-03 10:42:27 | BUILDING PLAN REVIEW- |
| | PERMIT: 08060519 |
| | ADD: 309 CLEMATIS ST |
| | CONT: WELLINGTON EQUESTRIAN |
| | TEL: (561)312-6247 JOHN WEBB |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | REVISION: DENIED |
| | |
| | 1) THE SUBMITTED REVISION INDICATES A NEW AUTOMATIC |
| | FIRE SHUTTER IN THE FRONT STAIRWELL BETWEEN THE 2ND AND |
| | 3RD FLOOR. THIS FIRE SHUTTER LEADS TO AN AREA THAT CAN |
| | BE CONSTRUED AS A MECHANICAL ROOM SINCE THIS WILL BE |
| | THE DOORWAY TO WORK ON THE EXISTING MECHANICAL |
| | EQUIPMENT BETWEEN THE EXISTING ROOFTOP AND THE NEW |
| | THIRD FLOOR ROOF TOP ADDITION. |
| | |
| | THE PERMIT SET OF PLANS LS-1 OR A2.0 DATED REVISION# 3 |
| | 5/11/09 DID NOT HAVE SUCH A DOORWAY IN THE VERTICAL |
| | EXIT STAIRWELL. PLEASE REVIEW: |
| | |
| | 2004 FBC-B 1020.5 PENETRATIONS ALLOWED IN THE STAIRWELL |
| | ARE LIMITED OR PROHIBITED EXCEPT FOR THE REQUIRED |
| | EXITDOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR |
| | INDEPENDENT PRESSURIZATION, SPRINKLER PIPING, |
| | STANDPIPES, ELECTRIC RACEWAYS, FOR FIRE DEPARTMENT |
| | COMMUNICATIONS AND ELECTRICAL RACEWAY SEERVING NOT MORE |
| | THE EXIT PASSAGEWAY AND TERMINATING AT A STEEL BOX NOT |
| | EXCEEDING 16 SQUARE INCHES. SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 712. |
| | |
| | THERE HAS BEEN MEETINGS ABOUT THIS PARTICULAR |
| | SITUATION, AND THE AGREEMENT WAS TO HAVE A VESTIBULE |
| | WITH TWO SETS OF 1 1/2 HR DOORS. THE INTENT WAS TO NOT |
| | HAVE A MECHANICAL ROOM OPEN DIRECTLY INTO THE STAIRWELL |
| | TRYING TO MEET THE INTENT OF 1020.5. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |