| 2010-11-30 09:14:58 | ROXY'S PUB |
| | 309 CLEMATIS STREET |
| | MASTER PERMIT NUMBER 08060519 |
| | REVISION TRACKING NUMBER 10110215 |
| | |
| | |
| | 1. ON SHEET A-1 IT WAS NOTED "OPENING TO BE PROTECTED |
| | BY A SELF-CLOSING 2 HOUR FIRE RATED SHUTTER ACTIVATED |
| | VIA FIRE ALARM OR POWER FAILURE". WHAT PREVENTS THE |
| | FIRE SHUTTER WHEN ACTIVATED FROM STRIKING PERSONS |
| | LOCATED IN THE ELEVATOR LOBBY OR PASSING THROUGH THE |
| | EXISTING STAIR # 1 OPENING THAT COMMUNICATES WITH THE |
| | ELEVATOR LOBBY. WHY IS NOT A FIRE RATED SIDE-SWINGING |
| | DOOR NOT BEING PLANNED FOR THIS LOCATION. THIS DOOR |
| | COULD REMAIN CLOSED AT ALL TIMES EXCEPT TO PASS THROUGH |
| | AND BE EQUIPPED WITH APPROPRIATE SIGNAGE INSTALLED TO |
| | PREVENT ACCIDENTS. THE OTHER PROBLEM THAT MAY POSE |
| | ISSUES FOR THE OWNER WITH THE FIRE SHUTTER BEING |
| | CONNECTED TO THE FIRE ALARM SYSTEM OR WHEN LOSS OF |
| | POWER OCCURS IS THE RE-SETTING OF THE FIRE SHUTTERS. |
| | SOMETIMES TECHNICIANS ARE NEEDED TO RE-SET THE SHUTTER |
| | WHICH COULD CREATE COST PROBLEMS. |
| | IF IT IS THE DESIRE TO INSTALL A FIRE SHUTTER ON THE |
| | FIRST FLOOR IT MAY BE CONSIDERED TO CONNECT IT TO SMOKE |
| | DETECTORS THAT ARE PROPRIETARY TO THE SHUTTER OR BE |
| | ACTIVATED BY A FUSIBLE LINK WHEREBY NUISANCE DROPS DO |
| | NOT OCCUR. PLEASE ADVISE SOLUTION AFTER HAVING |
| | CONSIDERING THIS INFORMATION. |
| | |
| | 2. THE FLORIDA FIRE PREVENTION CODE (NFPA 101) SECTION |
| | 9.4.7 INDICATES THAT "CONVEYORS, ELEVATORS, |
| | DUMBWAITERS, AND PNEUMATIC CONVEYORS SERVING VARIOUS |
| | STORIES OF A BUILDING SHALL NOT OPEN TO AN EXIT. |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |