| 2010-12-10 13:53:13 | PLANNING AND ZONING: ***** FAILED**** |
| | |
| | |
| | 1. RESPOND TO COMMENTS IN WRITING. |
| | |
| | 2. A MINOR AMENDMENT TO THE INFORMAL SITE PLAN REVIEW |
| | APPROVAL ("ISPR 05-09") IS REQUIRED. AN APPLICATION |
| | WILL NEED TO BE FILED TO THE PLANNING AND ZONING |
| | DEPARTMENT AND APPROVED PRIOR TO SIGN-OFF OF BUILDING |
| | PERMIT. YOU CAN DOWNLOAD AN APPLICATION AT THE LINK |
| | BELOW: |
| | |
| | HTTP://WWW.WPB.ORG/PLAN/INDEX.PHP?PAGE=PB, SCROLL TO |
| | THE MIDDLE OF THE PAGE AND DOWNLOAD THE DEVELOPMENT |
| | APPLICATION (SEE PAGE 2, SITE PLAN AMENDMENT (MINOR - |
| | LEVEL 1) FOR APPLICATION REQUIREMENTS. |
| | |
| | THE COMMENTS BELOW REFLECT THE INFORMATION NEEDED ON |
| | SITE PLAN, PRIOR TO SUBMITTAL OF THE MINOR AMENDMENT TO |
| | THE ISPR 05-09. |
| | |
| | 3. ON SHEET C4, "GENERATOR COMPOUND CROSS SECTION," |
| | INCLUDE THE GENERATOR PROFILE WITHIN THE ENCLOSURE TO |
| | ASSURE THAT THE ENTIRE GENERATOR WILL BE SCREENED. ALSO |
| | SHOW DETAIL OF LANDSCAPING AND CURBING WITH THE CROSS |
| | SECTION. |
| | |
| | THE SITE PLAN SHALL INCLUDE THE FOLLOWING: |
| | |
| | A. SCREENING AND ELEVATION OF WALL/HEDGES AROUND |
| | GENERATOR/ FUEL TANK, AND SETBACK DISTANCE FROM |
| | PROPERTY LINES. |
| | |
| | B. SHOW AMENDED SITE DATA TABLE THAT DEPICTS THE TOTAL |
| | PARKING SPACES THAT WERE REQUIRED/PROVIDED AND INCLUDE |
| | THE DELETION (MINUS) OF THE PARKING SPACES THAT WILL BE |
| | TAKEN UP BY THE NEW GENERATOR. A TERMINAL LANDSCAPE |
| | ISLAND WILL BE REQUIRED ON BOTH SIDES OF THE GENERATOR |
| | ENCLOSURE, SO ADDITIONAL PARKING WILL BE TAKEN UP. |
| | THERE SEEMS TO BE EXCESS PARKING FROM THE APPROVED |
| | PLANS, BUT THE REVISIONS SHOWING WHAT WAS REQUIRED AND |
| | PROVIDED NEED TO ALSO BE SHOWN. A COPY OF THE APPROVED |
| | PLANS CAN BE PROVIDED AT YOUR REQUEST FOR REFERENCE. |
| | |
| | NOTE: IS IT POSSIBLE TO MOVE THE GENERATOR OUT OF THE |
| | GENERAL PARKING AREA TO A MORE CONSPICUOUS AREA SUCH AS |
| | THE SOUTHEASTERN CORNER OF THE PROPERTY (WHERE THERE |
| | ARE SIX (6) PARKING SPACES)? THERE ARE TWO EXISTING |
| | LANDSCAPE TERMINAL ISLANDS IN PLACE THAT CAN |
| | ACCOMMODATE THE PROPOSED GENERATOR WITH LESS |
| | CURBING/LANDSCAPING ISLANDS REQUIRED. |
| | |
| | 4. PURSUANT TO SECTION 94-444(B) OPEN SPACE |
| | STANDARDS: |
| | |
| | (B) FUEL OR OIL OR PROPANE TANKS, GENERATORS SHALL NOT |
| | BE PERMITTED UNLESS APPROPRIATE SCREENING IS PROVIDED. |
| | SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE |
| | CONCRETE, OTHER |
| | DECORATIVE MASONRY, OR COMPARABLY, DURABLE WOOD AND |
| | STEEL. |
| | |
| | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES |
| | PLANTED AT TWO-FOOT INTERVALS. A FOUR-SIDED ENCLOSURE |
| | WITH MASONRY, OR COMPARABLY DURABLE WOOD AND STEEL, AN |
| | OBSCURING GATE IS REQUIRED AS A CONDITION FOR SITE PLAN |
| | APPROVAL. |
| | |
| | THE SCREENING SHALL ENCLOSE BOTH FUEL TANK AND ROOFTOP |
| | EXHAUST. |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| | |