| Plan Review Notes For Permit 10110181 |
| Permit Number |
10110181 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-17 10:49:50 | 1920 WEKIVA WAY | | | PERMIT NUMBER 10110181 | | | GENERATOR INSTALLATION | | | | | | 1. ALL ELECTRICAL WORK TO COMPLY WITH NFPA 70, THE | | | NATIONAL ELECTRICAL CODE. | | | | | | 2. ENTIRE GENERATOR INSTALLATION TO COMPLY WITH NFPA | | | 110. | | | | | | 3. PLANS DO NOT CONTAIN ANY STAMPS FROM THE DEPARTMENT | | | OF ENVIRONMENTAL RESOURCE MANAGEMENT (DERM). | | | | | | 4. PLEASE PROVIDE AN APPROVED SURVEY OF THE PROPOSED | | | PROPERTY WHERE THE GENERATOR IS TO BE INSTALLED. | | | | | | 5. APPROPRIATE SIGNAGE IS REQUIRED TO BE ON THE PLANS. | | | THIS SIGNAGE SHALL INCLUDE THE NFPA 704 DIAMONDS, "NO | | | SMOKING" SIGNS, PRODUCT NAME AND QUANTITY OF THE DIESEL | | | FUEL. | | | | | | 6. PLEASE INDICATE ON THE PLANS WHAT EQUIPMENT THE | | | GENERATOR IS EXPECTED TO RUN. IS IT LIFE SAFETY | | | EQUIPMENT ONLY OR GENERAL LOADS OR BOTH AND PLEASE | | | INDICATE DURATION. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | | | | |
|