| 2010-12-10 07:56:47 | SEPARATE SUBMITTAL IS REQUIRED TO: |
| | ENGINEERING SERVICES DEPARTMENT |
| | 401 CLEMATIS STREET, 4TH FLOOR |
| | WEST PALM BEACH, FL 33401 |
| | (MAILING ADDRESS: P.O. BOX 3366, ZIP 33402) |
| | MAIN PHONE: (561) 822-1200 |
| | DIRECT: (561) 494-1098 |
| | FAX: (561) 494-1116 |
| | WWW.WPB.ORG/ENGINEERING |
| | PLEASE GO TO THE LINK BELOW, |
| | HTTP://WWW.CITYOFWPB.COM/ENGINEERING/ENG_FORMS.PHP |
| | DEVELOPMENT PERMIT PACKAGE 2010 |
| | WILL GIVE YOU INSTRUCTIONS AND DOCUMENTATION REQUIRED |
| | FOR YOUR SUBMITTAL. |
| | |
| | SPECIFIC SITE COMMENTS: |
| | #1 WATER SERVICE TO THE PROPERTY IS 3/4" DIAMETER |
| | COPPER LINE. |
| | PLANS CALL FOR A 2". NEW TAP MAY BE REQUIRED BASED ON |
| | YOUR WATER DEMAND |
| | CALCULATION. (PLEASE SUPPLY DOCUMENTATION WITH PEAK |
| | WATER DEMAND). |
| | PLEASE TAKE INTO ACCOUNT CAR WASH EQUIPMENT, PUMPS, |
| | TANKS, ETC.) |
| | |
| | #2 BACKFLOWS ARE REQUIRED TO BE AS CLOSE TO THE SOURCE |
| | METER AS POSSIBLE, |
| | 18" MAX DISTANCE. |
| | |
| | #3 SEPERATE WATER SERVICE FOR IRRIGATION IS RECOMMENED |
| | AS SEWAGE PROCESSING |
| | WILL BE CHARGE BASED ON DOMESTIC WATER METER |
| | CONSUPTION. |
| | |
| | #4 PROVIDE A "SURFACE WATER MANAGEMENT REPORT". |
| | |
| | #5 SOUTHERN BLVD IS AN FDOT ROAD, PERMIT FOR UTILITY |
| | INSTALLTION MAY BE REQUIRED. |
| | DRIVEWAY ENTRANCE MODIFICATIONS WILL ALSO REQUIRE |
| | PERMITTING. |
| | |
| | #6 THE DRIVEWAY ON OLIVE AVE WILL REQUIRE TRUNCATED |
| | DOMES (ADA) ON EITHER SIDE. |
| | 2' WIDE X THE FULL WIDTH OF SIDEWALK. |
| | |
| | #7 ON SHEET C1, SHEET 1 OF 10 YOU CALL OUT SECTION AA, |
| | SECTION BB, AND SECTION DD HOWEVER IT SEEMS TO BE |
| | MISSING. |
| | PLEASE MAKE REFERENCE THAT THEY APPEAR ON SHEET C8, |
| | SHEET 8 OF 10. |
| | |
| | #8 PERVIOUS PAVER SYSTEM IS NOT AN APPROVED METHOD OF |
| | DRAINAGE WITHIN THE CITY OF WPB. |
| | SUPPLY ALTERNATE SYSTEM OF DRAINAGE. |
| | |
| | #9 A NEW CLEAN-OUT NEEDS TO BE INSTALLED AT CONNECTION |
| | POINT AND AT EVERY 75'. |
| | ANOTHER CLEAN-OUT JUST AFTER PIPE EXITS BUILDING. |
| | PIPE COLOR CODED TO DESIGNATE SEWAGE. |
| | |
| | #10 PROVIDE ENVIRONMENTAL SUMMARY OF SITE PREVIOUS USE |
| | AND IF ANY ENVIRONMENTAL REMEDIATION IS REQUIRED. |
| | (FOR EXAMPLE EXISTING UNDERGROUND TANKS, WELL POINTS, |
| | MONITORING WELLS, ETC.) |
| | |
| | #11 PROVIDE INFORMATION ON CARWASH SYTEM OR SUMMARY |
| | DESCRIBING PUMPS, TANKS, CISTERNS, ALL INTERNAL |
| | PROCESSES, ETC |
| | |
| | #12 IDENTIFY LOCATION OF "DRYWELL" ON THE CIVIL PLANS. |
| | |
| | #13 WHERE DO ROOF DRAINS DISCHARGE TO? |
| | |
| | #14 PROVIDE CITY STANDARD BACKFLOW DETAIL. STANDARD |
| | SIDEWALK DETAILS, ETC |
| | |
| | #15 PLEASE INCLUDE PERVIOUS AND IMPERVIOUS TOTALS |
| | (SF,AC) ON PAVING PLAN C1, SHEET 1 OF 10. |
| | |
| | PLEASE, RESPOND TO ALL COMMENTS IN WRITING. THANKS! |
| | ******************************************************* |
| | ********************************************** |