| 2010-11-19 10:42:24 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBC FLORIDA BUILDING CODE 2007 WITH 2009 SUPPLEMENTS |
| | FBC EB FLORIDA BUILDING CODE 2007 EXISTING BUILDING |
| | CODE |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FS FLORIDA STATUTE |
| | |
| | 1. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | ALL COMPONENTS AND CLADDING, FAC9B72: LOUVERS, OVERHEAD |
| | DOORS, ROOF TILE, BUILT UP ROOF, ROOF HATCH, ETC. |
| | PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL. |
| | |
| | 2. EQUIPMENT ROOM AND WASH AREA SHOWS EXITING THROUGH A |
| | STORAGE ROOM. SEE FBC1014.2(2). |
| | |
| | 3. SHOW ACCESSIBILITY FOR THE EMPLOYEE BATHROOM. SEE |
| | FBC CH 11 FOR TURNING RADIUS, CLEAR FLOOR SPACE FOR |
| | FIXTURES, FIXTURE REQUIREMENTS. THESE DETAILS ARE SHOWN |
| | FOR THE PUBLIC BATHROOMS BUT NOT FOR THE EMPLOYEE |
| | BATHROOM. |
| | |
| | 4. IMPACT FEE ASSESSMENT BY PALM BEACH COUNTY REQUIRED. |
| | THE PLANS ARE TO BE STAMPED AND THE RECEIPT, IF FEES |
| | ARE DUE, PROVIDED. 561-233-5025 FOR MORE INFORMATION. |
| | |
| | 5. REVISE EXPOSURE CATEGORY TO EXPOSURE C OR PROVIDE |
| | ENGINEERING ANALYSIS FOR THIS PARCEL WHICH IS LOCATED |
| | IN A TRANSITION ZONE, SEE ASCE7-05 6.5.6.5, FBC1609.4, |
| | PLEASE SEE AERIAL. |
| | |
| | 6. PERMIT VALUE IS TO INCLUDE ALL LABOR AND MATERIALS. |
| | PROVIDE A REASONABLE VALUE. |
| | |
| | |
| | |
| | |