 1. WRONG CODES LISTED ON SHEET E-1. WRONG EDITIONS OF
 THE FLORIDA BUILDING CODE AND THE FLORIDA FIRE
 PREVENTION CODE. SHOULD READ 2007 EDITIONS.
  
 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM SYSTEMS.
  
 3. TACTILE SIGNAGE REQUIRED AT EXIT DOORS.
  
 4. DOORS LOCATED IN EXISTING FIRE WALLS ARE TO BE FIRE
 RATED. NO DOOR SCHEDULE PROVIDED.
  
 5. EXITING APPEARS TO BE OCCURING THROUGH THE CONFERNCE
 ROOM. THERE DOES NOT APPEAR TO BE ENOUGH WIDTH AFTER
 SCALING THE AREA BETWEEN THE TABLE AND OTHER FURNITURE.
  
 6. ON SHEET A-2 SOME AREAS ARE NOT COVERED BY FIRE
 SPRINKLERS. THEY INCLUDE HALL 120, EXISTING TOILET 106,
 UTILITY 109, CLOSET 110, AND EXISTING TOLIET 118.
 PLEASE REVIEW THESE AREAS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  