| Plan Review Notes For Permit 10110108 |
| Permit Number |
10110108 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-17 07:40:09 | 4700 NORTH CONGRESS AVENUE, SUITE 100 | | | PERMIT NUMBER 10110108 | | | | | | 1. WRONG CODES LISTED ON SHEET E-1. WRONG EDITIONS OF | | | THE FLORIDA BUILDING CODE AND THE FLORIDA FIRE | | | PREVENTION CODE. SHOULD READ 2007 EDITIONS. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM SYSTEMS. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOORS. | | | | | | 4. DOORS LOCATED IN EXISTING FIRE WALLS ARE TO BE FIRE | | | RATED. NO DOOR SCHEDULE PROVIDED. | | | | | | 5. EXITING APPEARS TO BE OCCURING THROUGH THE CONFERNCE | | | ROOM. THERE DOES NOT APPEAR TO BE ENOUGH WIDTH AFTER | | | SCALING THE AREA BETWEEN THE TABLE AND OTHER FURNITURE. | | | | | | 6. ON SHEET A-2 SOME AREAS ARE NOT COVERED BY FIRE | | | SPRINKLERS. THEY INCLUDE HALL 120, EXISTING TOILET 106, | | | UTILITY 109, CLOSET 110, AND EXISTING TOLIET 118. | | | PLEASE REVIEW THESE AREAS. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | |
|