| Date |
Text |
| 2010-11-09 18:14:37 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PLEASE REVISE PLAN TO STATE BUILDING TYPE, FBC |
| | CHAPTER 6. SHEET A1 SHOWS A WOOD NAILER ABOVE THE |
| | CEILING; ARE COMBUSTIBLES PERMITTED IN THIS MANNER? |
| | |
| | 2. FBC 435.5.1, ROOM 103, NO SHIELDING SHOWN ON |
| | CORRIDOR OR TENANT SEPARATION WALLS OR THE DOOR BETWEEN |
| | THE CORRIDOR AND X-RAY ROOM. THIS METHOD OF RADIATION |
| | PROTECTION IS TO BE APPROVED WITH THE FLORIDA |
| | DEPARTMENT OF HEALTH (BASED ON DISTANCE, RADIATION |
| | PRODUCED, ETC.) PRIOR TO PERMIT ISSUANCE. WILL FILM |
| | ALSO BE PROCESSED IN THIS ROOM? SEE FBC435.5.2. |
| | |
| | 3. FBC 435.5.3, REVISE PLAN TO INCLUDE ALL REQUIRED |
| | INFORMATION AND SUBMIT TO DOH. PLEASE CONTACT THOMAS H. |
| | TOMCZAK, 904-278-5730, [email protected] |
| | FOR MORE INFORMATION. |
| | |
| | 4. PROVIDE INFORMATION REGARDING EXISTING OR PROPOSED |
| | NEW ACCESSIBLE ELEMENTS PER FBC11-4.1.6(2) SUCH AS: |
| | ACCESSIBLE ENTRANCE |
| | ROOM 103, SHOW MANEUVERING CLEARANCE FOR DOOR, PULL |
| | SIDE FBC 11 FIGURE 25 |
| | ACCESSIBLE DRINKING FOUNTAIN |
| | |
| | PROVIDE COST BREAKDOWN IF NECESSARY. |
| | |
| | 5. PROVIDE INFORMATION REGARDING PROPOSED NEW HARDWARE, |
| | FBC11-4.13.9. |
| | |
| | 6. PROVIDE MORE INFORMATION REGARDING PROPOSED USE OF |
| | CONFERENCE ROOM AND SINK. EITHER REVISE PLAN TO SHOW |
| | USE AS A WORK AREA OR PROVIDE A DETAIL TO COMPLY WITH |
| | FBC11-4.24. |
| | |
| | 7. AFTER DOH APPROVAL, AND DISCUSSION WITH DESIGNER OF |
| | RECORD, THIS REVIEW CAN BE ISSUED WITH PROVISO. |
| | |
| | |