2010-11-10 16:06:201645 PALM BEACH LAKES BOULEVARD, SUITE #700
 PERMIT #10110051
 MASTER #10060420
  
 REVIEW COMMENTS - FIRE
  
 1) CARD READER DESIGNATED "R7-2" PREVENTS ACCESS TO THE
 SECONDARY EXIT (STAIR #1). ANY LOCKING MECHANISM ON
 THIS DOOR IS PROHIBITED DUE TO THE LOCATION OF THE DOOR
 IN RELATION TO STAIR #1.
  
 2) THE ACTIVATION OF THE BUILDING SPRINKLER SYSTEM OR
 FIRE ALARM SYSTEM IS REQUIRED TO RELEASE THE MAGNETIC
 LOCKS PER SHEET NOTES 6, 7 AND 8. WHICH CONTRACTOR
 (FIRE ALARM OR SECURITY) IS RESPONSIBLE FOR THE
 INTEGRATION OF THE SECURITY RELAY MODULES TO THE FIRE
 ALARM SYSTEM?
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
 (561) 805-6730