Plan Review Notes
Plan Review Notes For Permit 10110019
Permit Number 10110019
Review Stop E
Sequence Number 1
Notes
Date Text
2010-11-10 20:20:47*************ELECTRICAL PLAN REVIEW FAIL***************
  
 1) SUBMIT ATS SPEC.SHEETS
 2) NEED PROFF OF PERMIT AND PERMIT NUMBER FOR EXISTING
 WORK
 3) TOTAL JOB COST MUST BE INCLUDED IN PERMIT APPLACTION
 INCLUDING VALUE OF GENERATOR AND TWO ATS SWITCHES THAT
 ARE EXISTING
  
  
 JOHN DICKINSON
 CONTRACT PLAN REVIEWER
 LICENSE NUMBER PX3182
 CELL 561-718-3230