| Plan Review Notes For Permit 10110008 |
| Permit Number |
10110008 |
|
| Review Stop |
G |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-05 14:40:05 | FBC 2007 FUEL GAS REVISION DENIED: | | | | | | 1. REVISED PLAN DOES NOT MATCH WITH ORIGINAL PLAN. | | | ORIGINAL PLAN SHOWS 2LB SYSTEM 36' AND 12" SYSTEM 86'. | | | REVISED PLAN DOES NOT SHOW A 2LB SYSTEM. | | | 2. TOTAL LOAD ON PLAN DATED 3/4/10 IS 513K BTU, ON | | | REVISION IT SHOWS EXISTING LOAD AS 428K BTU. | | | 3. THE 3 NEW LIGHTS AT THE TOP OF DRAWING SEEM TO BE | | | FED FROM 2 DIFFERENT PLACES. | | | 4. VALVES ARE NOT SHOWN FOR NEW LIGHTS. | | | | | | COPY OF ORIGIONAL PLAN IS IN REVISION PACKAGE. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | |
|