| Plan Review Notes For Permit 10100665 |
| Permit Number |
10100665 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-01 15:37:35 | *******PLAN DENIED******** | | | 1)ELECTRIC PLAN IS REQUIRED TO BE SIGNED BY DESIGNE | | | ALSO LICENSE NUMBER | | | 2) SHOW WHAT SIZE EXISTING SERVICE ENTRANCE CONDUCTORS | | | ARE IN EXISTING RISER | | | 2) SUBMMIT LOAD CALCUATIONS SHOUING NEW 10KW HEAT STRIP | | | AND ALL EXISTING LOADS | | | JOHN DICKINSON | | | CONTRACT PLAN REVIEWER | | | CELL NUMBER 561-718-3230 |
|