| Notes |
| Date |
Text |
| 2010-11-01 17:08:18 | ************ELECT DENIED************* | | | 1)PAPER WORK FOR ATS DOES NOT SHOW A UL OR OTHER | | | APPROVED TEST LAB. | | | 2) SUBMIT A RISER DIAGRAM SHOWING ALL MAIN SERVICE | | | ELECTRICAL EQUIPMENT. | | | 3) ELECTRICAL PLAN IS REQUIRED TO HAVE DESIGNERS NAME, | | | LICENSE MUMBER,AND BE SIGNED | | | 4) SHOW LOADS BEING SERVED | | | 5) SUBMIT LOAD CALCUATIONS ON GENERATOR | | | 6) SUBMIT SERVEY SITE PLAN SHOWING GENERATOR LOCATION | | | AND EXHUST IN REFERANCE TO ANY BUILDING OPENINGS | | | DOORS,WINDOWS,VENTS. | | | JOHN DICKINSON | | | CONTRACT PLAN REVIEWER CITY OF WEST PALM BEACH | | | CELL PHONE 561-718-3232 | | | |
|