| 2010-11-09 10:28:19 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. PER ARCHITECT, CASEMENT WINDOWS WILL BE INSTALLED IN | | | LOCATIONS MARKED "EGRESS". REVISE WINDOW SCHEDULE. | | | | | | 2. REVISE PLAN TO SHOW BOND BREAK FOR STUCCO, FBC | | | R703.6.3, DETAILS 2 AND 3 A3.1. | | | | | | 3. DETAILS 2 AND 3, SHEET A3.1, 4D NAILS SPECIFIED FOR | | | LATH ATTACHMENT. SEE FBC R703.6.2, A MINIMUM OF 1 3/4" | | | PENETRATION REQUIRED INTO STRUCTURAL MEMBER PER ASTM | | | C1063. PLEASE REVISE ALL AFFECTED DETAILS. | | | | | | 4. S1.1, OUTDATED ASCE7 REFERENCE, FBC R 43, PLEASE | | | REVISE. | | | | | | 5. PRODUCT APPROVAL 05-0311.01 (AWP SERIES 1700), FL474 | | | (SIMPSON CONNECTORS) AND FL 3341 (FLEMING DOOR) ARE | | | EXPIRED AND HAVE BEEN REMOVED. SUBMIT CURRENT PRODUCT | | | APPROVALS WITH THE REVISION AS NECESSARY. | | | | | | | | | |
|