Plan Review Notes
Plan Review Notes For Permit 10100654
Permit Number 10100654
Review Stop B
Sequence Number 2
Notes
Date Text
2010-11-09 10:28:19****PROVISO****
 ****REVISION REQUIRED****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PER ARCHITECT, CASEMENT WINDOWS WILL BE INSTALLED IN
 LOCATIONS MARKED "EGRESS". REVISE WINDOW SCHEDULE.
  
 2. REVISE PLAN TO SHOW BOND BREAK FOR STUCCO, FBC
 R703.6.3, DETAILS 2 AND 3 A3.1.
  
 3. DETAILS 2 AND 3, SHEET A3.1, 4D NAILS SPECIFIED FOR
 LATH ATTACHMENT. SEE FBC R703.6.2, A MINIMUM OF 1 3/4"
 PENETRATION REQUIRED INTO STRUCTURAL MEMBER PER ASTM
 C1063. PLEASE REVISE ALL AFFECTED DETAILS.
  
 4. S1.1, OUTDATED ASCE7 REFERENCE, FBC R 43, PLEASE
 REVISE.
  
 5. PRODUCT APPROVAL 05-0311.01 (AWP SERIES 1700), FL474
 (SIMPSON CONNECTORS) AND FL 3341 (FLEMING DOOR) ARE
 EXPIRED AND HAVE BEEN REMOVED. SUBMIT CURRENT PRODUCT
 APPROVALS WITH THE REVISION AS NECESSARY.
  
  
  