| 2010-11-04 09:18:55 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. ONLY ONE COMPLETE SET OF PLANS SUBMITTED. UPON |
| | ISSUANCE, CONTRACTOR IS TO REQUEST INSPECTION SETS FROM |
| | CSD RECORDS. |
| | |
| | 2. ARCHITECT'S RESPONSE LETTER STATES THAT CASEMENT |
| | WINDOWS WILL BE INSTALLED, BUT PLANS SHOW ONLY SINGLE |
| | HUNG. SEE FBC EXISTING BUILDING 604.1 REGARDING WINDOW |
| | REPLACEMENT, BEDROOM EGRESS REQUIREMENTS AND EXCEPTION. |
| | |
| | 3. BOND BREAK REQUIRED, FBC R703.6.3, DETAILS 2 AND 3 |
| | A3.1. PLANS WERE REVISED TO SHOW 30# PAPER OVER |
| | SHEATHING, BUT ONE LAYER OF 30# OVER PLYWOOD DOES NOT |
| | COMPLY WITH THE BOND BREAK REQUIREMENT. PLEASE REVISE |
| | AND CHECK ALL DETAILS. |
| | |
| | 4. DETAILS 2 AND 3, SHEET A3.1, 4D NAILS SPECIFIED FOR |
| | LATH ATTACHMENT. SEE FBC R703.6.2, A MINIMUM OF 1 3/4" |
| | PENETRATION REQUIRED INTO STRUCTURAL MEMBER PER ASTM |
| | C1063. PLEASE REVISE AND CHECK ALL DETAILS. |
| | |
| | 5. FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED FOR |
| | DOORS, WINDOWS, AND MULLIONS FAC9B72. |
| | TRANSMITTAL/RESPONSE LETTER MAKES REFERENCE TO VARIOUS |
| | PRODUCT APPROVALS BUT THE PRODUCT APPROVALS WERE NOT |
| | SUBMITTED. |
| | |
| | 6. S1.1, OUTDATED ASCE7 REFERENCE, FBC R 43, PLEASE |
| | REVISE. |
| | |
| | 7. ISSUANCE WITH PROVISO CAN BE CONSIDERED UPON |
| | ARCHITECT'S REQUEST. |
| | |
| | |
| | |
| | |