| 2010-11-16 18:35:17 | 1) SUBMIT MODEL NUMBERS OF NEW LIGHTING FIXTURES. | | | 2) SUBMIT LIGHTING DENSITIE CALCULATIONS AS PER | | | 13-415.ABC 2007 F.B.C. | | | 3) SHOW LOCATION OF EXISTING PANELS. | | | 4) DO NOT UNDERSTAND RISER DIAGRAM,PLEASE REDRAW | | | SHOWING ORDER OF EQUIPMENT. | | | 5) SHOW SIZE OF MAIN FEEDERS FROM 600 AMP MAIN TO | | | PANELS. | | | 6) PANEL SCHEDULE SHOWS PANEL B AS BEING 100 AMP BUS. | | | | | | JOHN DICKINSON | | | CONTRACT PLAN REVIEWER | | | CELL NUMBER 561-718-3230 |
|