2010-10-26 10:59:27RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- FLAT ROOF ASSEMBLY:
 A) PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS FOR
 NAIL ENHANCING AT PERIMETER AND CORNER AREAS AS
 REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA
 07-1203.01 SUBMITTED. NEED NAIL ENHANCING TO MEET THE
 DESIGN PRESSURES OF SEC. R301 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 B) DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO 2009
 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 C) ACCORDING TO MIAMI-DADE WEBSITE THE FILE FOR NOA
 07-1203.01 SUBMITTED WAS SUPERSEDED. GO TO THE
 MIAMI-DADE WEBSITE AND DOWNLOAD CURRENT NOA.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712