| Plan Review Notes For Permit 10100582 |
| Permit Number |
10100582 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-09 07:34:47 | 6600-45TH STREET | | | PERMIT NUMBER 10100582 | | | NEW BULK STORAGE TANK FOR SULFURIC ACID | | | | | | | | | 1. THE INSTALLATION FOR THE STORAGE, HANDLING, AND USE | | | SHALL COMPLY WITH THE FLORIDA FIRE PREVENTION CODE | | | (NFPA 1) CHAPTER 60 HAZARDOUS MATERIALS. | | | | | | 2. NO SMOKING IS PERMITTED WITHIN 25 FEET OF THE | | | OUTDOOR STORAGE AREA. APPROPRIATE SIGNAGE IS TO BE | | | PROVIDED REGARDING THE NO SMOKING REQUIREMENTS OF | | | CHAPTER 60. | | | | | | 3. HAZARD IDENTIFICATION SIGNAGE (NFPA 704) SHALL BE | | | PROVIDED FOR THE BULK STORAGE SULFURIC ACID STORAGE | | | TANK. | | | | | | 4. INCOMPATIBLE MATERIALS ARE TO BE KEPT AWAY FROM THE | | | SULFURIC ACID PRODUCT. | | | | | | 5. ALL UNNECESSARY COMBUSTIBLE MATERIALS ARE TO BE KEPT | | | AWAY FROM THE BULK STORAGE AREA OF THE SULFURIC ACID. | | | | | | 6. THE HAZARDOUS MATERIALS MANAGEMENT PLAN (HMMP) SHALL | | | BE REVIEWED PERIODICALLY TO ENSURE CORRECTNESS. | | | | | | | | | APPROVED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|