| 2010-11-04 14:03:33 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | FROM PREVIOUS LIST: |
| | |
| | 1. STATE WIND DESIGN CRITERIA (COMPONENT & CLADDING |
| | DESIGN PRESSURE REQUIREMENT) FOR THE NEW DOOR, |
| | FBC1603.1.4. |
| | |
| | 2ND REVIEW, PLEASE REVISE TO EXPOSURE C PER AERIAL OR |
| | CONTACT ME TO DISCUSS. |
| | |
| | 2. FBC TABLE 715.4, FIRE RATED WALLS NOT SHOWN ON THE |
| | PLAN. PLEASE NOTE RATED WALLS (OCCUPANCY SEPARATION |
| | BETWEEN BUSINESS AND S2) AND SHOW COMPLIANCE FOR THE |
| | DOOR IF APPLICABLE. |
| | |
| | 2ND REVIEW, FIRE SHUTTER IS NOW SHOWN OVER PROPOSED NEW |
| | GLAZED DOOR. IT APPEARS THAT THIS DOOR IS IN THE MEANS |
| | OF EGRESS, AND IS THE ONLY WAY TO EXIT THE ELEVATOR |
| | LOBBY IN THIS HIGH RISE BUILDING. ALSO NOTE THAT IT IS |
| | LIKELY THAT TWO EXITS ARE REQUIRED, AND ONE EXIT WOULD |
| | BE BLOCKED BY OPERATION OF THE FIRE SHUTTER. PLEASE |
| | PROVIDE A LIFE SAFETY PLAN TO SHOW HOW THIS CHANGE IN |
| | THE MEANS OF EGRESS AFFECTS EXITING (TRAVEL DISTANCE, |
| | REQUIRED EXITS, COMMON PATH, ETC., FBC CH 10). |
| | |
| | PLEASE NOTE THAT A FIRE DEPARTMENT REVIEW WILL BE |
| | REQUIRED AFTER SUBMISSION OF THE LIFE SAFETY PLAN. |
| | |
| | 3. PROVISO ITEM, SUBJECT TO FIELD INSPECTOR'S |
| | DISCRETION, A DETAIL PREPARED OR REVIEWED BY THE |
| | ARCHITECT FOR THE RAISED (EXISTING) DRAIN AND SLOPED |
| | CONCRETE TRANSITION MAY BE REQUIRED. |
| | |
| | 4. PROVISO ITEM, RE: A1, NOTE 5, "REMOVE AND REPLACE |
| | FIRE ALARM AND EMERGENCY DEVICES," ANY ALTERATIONS TO |
| | THE EXISTING FIRE ALARM SYSTEM SHALL BE UNDER SEPARATE |
| | PERMIT AND REVIEW. |
| | |
| | |
| | |