| Plan Review Notes For Permit 10100535 |
| Permit Number |
10100535 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-21 08:31:37 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. STATE WIND DESIGN CRITERIA (COMPONENT & CLADDING | | | DESIGN PRESSURE REQUIREMENT) FOR THE NEW DOOR, | | | FBC1603.1.4. | | | | | | 2. FBC TABLE 715.4, FIRE RATED WALLS NOT SHOWN ON THE | | | PLAN. PLEASE NOTE RATED WALLS (OCCUPANCY SEPARATION | | | BETWEEN BUSINESS AND S2) AND SHOW COMPLIANCE FOR THE | | | DOOR IF APPLICABLE. | | | | | | 3. PROVISO ITEM, SUBJECT TO FIELD INSPECTOR'S | | | DISCRETION, A DETAIL PREPARED OR REVIEWED BY THE | | | ARCHITECT FOR THE RAISED (EXISTING) DRAIN AND SLOPED | | | CONCRETE TRANSITION MAY BE REQUIRED. | | | | | | 4. PROVISO ITEM, RE: A1, NOTE 5, "REMOVE AND REPLACE | | | FIRE ALARM AND EMERGENCY DEVICES," ANY ALTERATIONS TO | | | THE EXISTING FIRE ALARM SYSTEM SHALL BE UNDER SEPARATE | | | PERMIT AND REVIEW. | | | |
|