| Plan Review Notes For Permit 10100534 |
| Permit Number |
10100534 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-01-19 07:58:19 | 2007 FBC W/2009 REVISIONS | | | | | | DENIED BY PLUMBING | | | | | | 1) THE PLUMBING RISER DIAGRAM ON A3 ONLY SHOWS ONE OF | | | THE TWO LAVATORIES LOCATED IN THE MASTER BATHROOM. | | | PLEASE REVISE THE DIAGRAM TO SHOW HOW THE SECOND | | | LAVATORY IS CONNECTED TO THE BUILDING DRAIN AND HOW IT | | | WILL BE VENTED. | | | | | | 2) ON A3 THE VENT TO ROOF FOR THE WASHING MACHINE DRAIN | | | IS SPECIFIED AS 2" ON THE PLUMBING RISER DIAGRAM AND 3" | | | ON THE FLOOR PLAN. PLEASE COORDINATE THE VENT SIZE. | | | | | | 3) ON A7 IN THE BUILDER NOTES AT THE BOTTOM OF THE | | | ELECTRICAL SYMBOL LEGEND THERE IS A NOTE THAT STATES | | | ALL PLUMBING SHALL COMPLY WITH THE 2004 FL PLUMBING | | | CODE. PLEASE UPDATE THIS NOTE TO THE 2007 FL PLUMBING | | | CODE. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|