| Plan Review Notes For Permit 10100534 |
| Permit Number |
10100534 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-03 09:50:03 | 2007 FBC W/2009 REVISIONS | | | 2008 NEC | | | | | | ELECTRICAL REVIEW DENIED | | | | | | 1) THE NAME AND LICENSE NUMBER OF THE PERSON | | | RESPONSIBLE FOR THE ELECTRICAL DESIGN IS REQUIRED TO BE | | | ON THE DRAWINGS. FS 471.003 | | | | | | 2) THE PLANS DO NOT COMPLY WITH 2008 NEC 210.52 FOR | | | REQUIRED RECEPTACLE SPACING. | | | | | | 3) SHOW COMPLIANCE WITH NEC 422.31 AND 422.32 FOR | | | DISCONNECTING MEANS AT A/C COMPRESSOR AND OTHER MOTOR | | | DRIVEN APPLIANCES OR PERMANENTLY CONNECTED APPLIANCES. | | | | | | 4) SHOW COMPLIANCE WITH NEC 406.11 FOR TAMPER-RESISTANT | | | RECEPTACLES. | | | | | | 5) SHOW COMPLIANCE WITH NEC 210.12 (B) FOR ARC-FAULT | | | CIRCUIT-INTERRUPTER PROTECTION IN FAMILY ROOMS, DINING | | | ROOMS, LIVING ROOMS, BEDROOMS, CLOSETS, HALLS AND OTHER | | | SIMILAR ROOMS OR AREAS. | | | | | | 6) NEC 210.8 REQUIRES ALL 125 -VOLT, SINGLE PHASE, 15- | | | AND 20- AMPERE RECEPTACLES INSTALLED IN GARAGES TO HAVE | | | GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION. THE | | | RECEPTACLE FOR THE GARAGE DOOR OPENER IS REQUIRED TO | | | COMPLY. | | | | | | 7) SHOW COMPLIANCE WITH FBC R313.4 WHICH REQUIRES | | | CARBON MONOXIDE ALARMS WITHIN 10 FEET OF EACH ROOM USED | | | FOR SLEEPING PURPOSES. | | | | | | 8) A PANEL SCHEDULE IN COMPLIANCE WITH NEC 408.4 IS | | | REQUIRED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|