| Plan Review Notes For Permit 10100399 |
| Permit Number |
10100399 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-04 10:29:42 | 525 SOUTH FLAGLER DRIVE | | | PERMIT #10100399 | | | | | | REVIEW COMMENTS: FIRE | | | | | | 1) PROVIDE FLOOR PLAN INDICATING WHICH DOORS WILL BE | | | REPLACED. | | | | | | 2) PROVIDE DOOR CLOSERS AND LISTED FIRE EXIT HARDWARE | | | FOR RATED DOORS. | | | | | | 3) PROVIDE DIRECTION OF DOOR SWING OF ALL EXIT DOORS. | | | | | | 4) PROVIDE UL FIRE RESISTANCE RATING OF PROPOSED DOORS. | | | APPLICATION STATES DOORS BE RATED AT 90- MINUTES. | | | | | | 5) TRANSOM OR WINDOWS ARE REQUIRED TO BE FIRE RATED ON | | | FIRE RATED DOORS. | | | | | | 6) IF ELECTRIC HARDWARE OR CONTROLED ACCESS IS INTENDED | | | TO BE USED PLEASE PROVIDE THIS INFORMATION. | | | | | | WJOLIN, DDANIELS | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | 561 805-6730 | | | | | | | | | | | | |
|