| 2010-11-08 10:14:04 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. THE METAL ROOF PRODUCT SUBMITTED HAS A DESIGN |
| | PRESSURE LIMITATION OF -30PSF. SEE SHEET S-5, -56.5 |
| | REQUIRED FOR ZONE 3, -48.4 REQUIRED FOR ZONE 2. |
| | |
| | 2. SEE BUILDING PROVISO #2, FAC9B72, PRODUCT APPROVALS |
| | REVIEWED BY DESIGNER OF RECORD REQUIRED FOR ALL |
| | COMPONENTS AND CLADDING. PLEASE HAVE THE ROOF PRODUCT |
| | APPROVALS REVIEWED PRIOR TO SUBMISSION. |
| | |
| | 3. PRIOR TO INSTALLATION, INVESTIGATE AND ADDRESS ANY |
| | POTENTIAL ISSUES WHICH MAY ARISE FROM DISSIMILAR METALS |
| | ON THE ROOF (METAL ROOF, COPPER FLASHING, ALUMINUM |
| | GUTTERS), R904.2. |
| | |
| | 4. BUILDING PROVISO #6, ENGINEER TO PROVIDE A LETTER OR |
| | REVISE THE PLAN TO CONFIRM THAT THE DESIGN CONFORMS TO |
| | THE REQUIREMENT OF FBC R301.2.1.4.3(2), "ROOF SHEATHING |
| | UPLIFT AND ROOF-TO-WALL UPLIFT LOADS SHALL BE INCREASED |
| | BY 20 PERCENT." PLEASE NOTE THAT SOME OF THE UPLIFT |
| | ANCHORS DO NOT APPEAR TO BE INCREASED ON THE PLAN |
| | SUBMITTED. THIS ITEM MUST BE ADDRESSED PRIOR TO |
| | INSTALLATION OF ROOF FRAMING COMPONENTS AND PRIOR TO |
| | ISSUANCE OF ROOF PERMIT. |
| | |
| | 5. UNDERLAYMENT PRODUCT APPROVAL SUBMITTED DOES NOT |
| | INCLUDE THE INSTALLATION INSTRUCTIONS/EVALUATION |
| | REPORT, FAC9B72. |
| | |
| | 6. THE ROOF METAL PRODUCT APPROVAL PROVIDED IS |
| | "VALIDATED," SHOULD BE "APPROVED." PLEASE PROVIDE |
| | CURRENT COVER SHEETS FOR ANY FLORIDA STATE PRODUCT |
| | APPROVALS SUBMITTED, FAC9B72, WWW.FLORIDABUILDING.ORG. |