| Plan Review Notes For Permit 10100391 |
| Permit Number |
10100391 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-11-02 11:56:17 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | ITEMS FROM PROVISO LIST: | | | | | | 1. ADDRESSED. | | | 2. PROVIDE A DETAIL FOR REQUIRED FIRE RATING, TENANT | | | SEPARATION. THIS INCLUDES HORIZONTAL AND VERTICAL, FBC | | | 708.1. IT APPEARS THAT HORIZONTAL SEPARATION WAS | | | REBUILT BETWEEN UNITS 4 AND 8, PLEASE ALSO NOTE | | | AFFECTED SEPARATION BETWEEN UNIT 8 AND STAIRS, | | | 3. ADDRESSED. | | | 4. SPECIFY SOFFIT VENTING | | | 5. DETAIL FOR WINDOW INFILL LACKS BOND BREAK | | | FBC1404.2.1. | | | | | | NEW COMMENTS: | | | | | | 6. PLAN SHOWS A NEW ENTRY DOOR. SEE FBC715.4, SPECIFY | | | REQUIRED FIRE RESISTANCE ON THE PLAN. | | | 7. PLEASE REVISE ASCE 7 REFERENCE TO CURRENT, | | | (ASCE7-05) OR EXPLAIN USE OF ASCE 7-02. FBC35 | | | | | | |
|