2010-10-21 13:09:431200-45TH STREET
 PERMIT NUMBER 10100266
 "PROVIDE AND INSTALL REPLACEMENT GENERATOR PER THE
 ATTACHED PLANS AND SPECS"
  
  
 1. PLEASE PROVIDE CUT SHEETS AND PRODUCT APPROVALS FOR
 THE NEW PERMANENT GENERATOR.
  
 2. PLEASE PROVIDE A CODE DATA TABLE REFERENCING THE
 APPROPRIATE CODES. (FLORIDA FIRE PREVENTION CODE, 2006
 EDITION, NFPA 37, NFPA 30, NFPA 110, NFPA 70)
  
 3. PLEASE DECLARE WHAT EQUIPMENT THE NEW EMERGENCY
 GENERATOR IS EXPECTED TO SUPPLY. IS IT ONLY LIFE SAFETY
 SYSTEMS AND DEVICES OR EMERGENCY SYSTEMS AND NON
 EMERGENCY SYSTEMS.
  
 4. PLEASE SUPPLY A SURVEY TO ENSURE THAT THE ORIGINAL
 INSTALLATION LOCATION IS NOT IN ANY RECORDED EASEMENTS,
 ON PROPERTY LINES, AND IT ALLOWS SETBACKS TO BE
 EXAMINED.
  
 5. PLEASE INDICATE ANY WARNING LABELS ON THE DIESEL
 FUEL STORAGE TANK.
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION