| Plan Review Notes For Permit 10100266 |
| Permit Number |
10100266 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-21 13:09:43 | 1200-45TH STREET | | | PERMIT NUMBER 10100266 | | | "PROVIDE AND INSTALL REPLACEMENT GENERATOR PER THE | | | ATTACHED PLANS AND SPECS" | | | | | | | | | 1. PLEASE PROVIDE CUT SHEETS AND PRODUCT APPROVALS FOR | | | THE NEW PERMANENT GENERATOR. | | | | | | 2. PLEASE PROVIDE A CODE DATA TABLE REFERENCING THE | | | APPROPRIATE CODES. (FLORIDA FIRE PREVENTION CODE, 2006 | | | EDITION, NFPA 37, NFPA 30, NFPA 110, NFPA 70) | | | | | | 3. PLEASE DECLARE WHAT EQUIPMENT THE NEW EMERGENCY | | | GENERATOR IS EXPECTED TO SUPPLY. IS IT ONLY LIFE SAFETY | | | SYSTEMS AND DEVICES OR EMERGENCY SYSTEMS AND NON | | | EMERGENCY SYSTEMS. | | | | | | 4. PLEASE SUPPLY A SURVEY TO ENSURE THAT THE ORIGINAL | | | INSTALLATION LOCATION IS NOT IN ANY RECORDED EASEMENTS, | | | ON PROPERTY LINES, AND IT ALLOWS SETBACKS TO BE | | | EXAMINED. | | | | | | 5. PLEASE INDICATE ANY WARNING LABELS ON THE DIESEL | | | FUEL STORAGE TANK. | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|