| 2010-12-10 13:24:16 | DENIED BY BUILDING |
| | |
| | 1) THE REVISED PLANS INCORRECTLY SPECIFY THE WIND-SPEED |
| | AS 120 MPH. THE CORRECT WIND-SPEED FOR WEST PALM BEACH |
| | IS 140 MPH AND THE EXPOSURE CATEGORY FOR THIS BUILDING |
| | IS C. PLEASE CORRECT. |
| | |
| | 2) THE COMPONENT AND CLADDING PRESSURES ARE TOO LOW FOR |
| | THE ADDITIONS TO THE MAIN HOUSE. THE PRESSURES NEED TO |
| | REFLECT THE 140 MPH WIND-SPEED, THE EXPOSURE CATEGORY C |
| | AND THE MEAN ROOF HEIGHT OF 26 FEET. |
| | |
| | 3) THE COMPONENT AND CLADDING PRESSURES ARE TOO LOW FOR |
| | THE ADDITIONS TO THE CABANA. THE PRESSURES NEED TO |
| | REFLECT THE 140 MPH WIND-SPEED, THE EXPOSURE CATEGORY C |
| | AND THE MEAN ROOF HEIGHT OF 26 FEET. |
| | |
| | 4) THE ELEVATIONS FOR THE CABANA ON A-02 SPECIFIES THE |
| | TOP OF THE PARAPET WALL AT THE ADDITION AS 34'-10". |
| | PLEASE CORRECT. |
| | |
| | 5) THE COMPONENT AND CLADDING PRESSURES FOR THE |
| | ADDITION ROOFS ARE INCORRECT. THE ADDITIONS ALL HAVE |
| | FLAT ROOFS AND THE EFFECTIVE WIND AREA IS 10 SQFT. IF |
| | USING TABLES R301.2(2) AND R301.2(3). |
| | |
| | 6) THE ENERGY CALCULATION FORMS ARE NOT SIGNED BY THE |
| | OWNER AGENT. THE FORMS HAVE THE EXTERIOR WALLS AS R-6 |
| | AND THE PLANS HAVE R-4. THE CEILING INSULATION ON THE |
| | FORMS IS R-30 AND THE PLANS HAVE R-19. PLEASE CORRECT. |
| | |
| | 7) THE ROOFING PRODUCT APPROVAL FOR THE JOHNS MANVILLE |
| | TORCH DOWN MODIFIED ROOF REQUIRES SIGNED AND SEALED |
| | CALCULATIONS FOR ENHANCED FASTENING FOR THE HIGHER |
| | UPLIFTS AT THE CORNER AND PERIMETER AREAS. SPECIFY THE |
| | APPROVED ASSEMBLY AND FASTENING OPTION FROM THE PRODUCT |
| | APPROVAL FOR A NON-INSULATED WOOD DECK THAT WILL BE |
| | INSTALLED AND SUBMIT THE ENHANCED FASTENING |
| | CALCULATIONS. |
| | |
| | 8) THE PLANS SPECIFY AN 1/8" PER FOOT SLOPE ON THE FLAT |
| | ROOFS. THE MINIMUM SLOPE ALLOWED BY THE CODE IS 1/4" |
| | PER FOOT PER FBC R905.11.1. PLEASE CORRECT. |
| | |
| | 9) SHOW COMPLIANCE WITH FBC R903.4.1 AND FBC PLUMBING |
| | 1107.1 - 1107.3 FOR SECONDARY (EMERGENCY) ROOF DRAINS. |
| | THESE ARE REQUIRED IN ADDITION TO THE PRIMARY DRAINS |
| | SHOWN ON THE REVISED DRAWINGS. |
| | |
| | 10) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. FBC 106.3.3 |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |