| 2010-10-27 07:54:55 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PLANS SPECIFY EXPOSURE CATEGORY B AND THE |
| | STRUCTURE IS LOCATED IN EXPOSURE CATEGORY C PER FBC |
| | R301.2.1.4.3. PLEASE REVISE PLANS. ALSO REVISE THE |
| | COMPONENT AND CLADDING PRESSURES TO COMPLY WITH |
| | EXPOSURE C. |
| | |
| | 2) THE PLANS WILL BE REQUIRED TO BE REVIEWED BY PALM |
| | BEACH COUNTY FOR IMPACT FEES. THIS CAN BE DONE AFTER |
| | ALL OF THE REVIEWS HAVE BEEN COMPLETED. |
| | |
| | 3) SUBMIT 2 COPIES OF ENERGY CALCULATIONS FOR THE NEW |
| | ADDITION AS REQUIRED BY 2007 FBC ENERGY GLITCH |
| | AMENDMENTS CHAPTER 11. THE FORM IS REQUIRED TO BE |
| | SIGNED BY THE PREPARER AND THE OWNER/AGENT. THE |
| | R-VALUES SPECIFIED ON THE PLANS ARE REQUIRED TO |
| | CORRESPOND WITH THE ENERGY CALC. FORM. |
| | |
| | 4) SECTION AA ON SHEET S-01 SPECIFIES 4" INSULATION ON |
| | 1/2" PT FURRING. PLEASE CLARIFY. DID YOU MEAN R-4 |
| | INSULATION ON 1 X 2 FURRING? |
| | |
| | 5) SHOW COMPLIANCE WITH FBC R806.1 FOR ROOF VENTILATION |
| | OR R806.4 FOR UNVENTED ATTIC ASSEMBLIES. |
| | |
| | 6) SHEET S-01 SPECIFIES A MODIFY STARCH DOWN BUILT-UP |
| | ROOF MEMBRANE. PLEASE CLARIFY. DID YOU MEAN A MODIFIED |
| | TORCH DOWN MEMBRANE. SUBMIT 2 COPIES OF PRODUCT |
| | APPROVALS FOR THE ROOF COVERING MATERIAL THAT WILL BE |
| | INSTALLED AS REQUIRED BY DCA RULE 9B-72. SPECIFY THE |
| | APPROVED ASSEMBLY AND FASTENING OPTION THAT WILL BE |
| | USED. IF THE DESIGN PRESSURES REQUIRE ENHANCED |
| | FASTENING FOR THE PERIMETER AND CORNER AREAS, SUBMIT |
| | ENHANCED FASTENING CALCULATIONS. |
| | |
| | 7) SHOW COMPLIANCE WITH FBC R903.4 AND R903.4.1 FOR |
| | ROOF SCUPPERS AND OVERFLOW SCUPPERS. SPECIFY THE SIZE |
| | OF THE ROOF AND OVERFLOW SCUPPERS AND PROVIDE SIZING |
| | CALCULATIONS. INCLUDE THE AREA OF THE ROOF ABOVE THAT |
| | WILL EMPTY ONTO THE FLAT ROOF BELOW. SEE FBC PLUMBING |
| | 1106.7 AND 1107.3. |
| | |
| | 8) DOWN SPOUTS ARE REQUIRED ON THE PRIMARY SCUPPERS AND |
| | SHALL DISCHARGE AT LEAST ONE FOOT AWAY FROM THE |
| | STRUCTURE SIDEWALL PER FBC R320.7. |
| | |