| 2010-10-28 20:21:22 | ***APPROVED WITH THE FOLLOWING PROVISOS**** | | | 1. ALL BRANCH CIRCUITS MUST BE PROTECTED WITH ARC FAULT | | | PROTECTION PURSUANT TO ARTICLE 210-12 (B) | | | 2. BOTH SMOKE AND CARBON MONOXIDE DETECTION SHALL BE | | | PROVIDED. HARD WIRED BATTERY BACKUP COMBINATION UNITS | | | MAY BE UTILIZED WITHIN 10 FEET OF ALL SLEEPING ROOMS | | | PURSUANT TO FBC-R AND NFPA-72. | | | 3. TAMPER RESISTANT RECEPTACLES ARE REQUIRED PURSUANT | | | TO ARTICLE 406.11 | | | 4. GFI PROTECTED WEATHER RESISTANT RECEPTACLES ARE | | | REQUIRED OUTSIDE THE STRUCTURE AT BOTH THE FRONT AND | | | REAR PURSUANT TO ARTICLE 210-52(E)(1) |
|