| 2010-10-20 16:02:04 | RESIDENTIAL (R3) ADDITION/RENOVATION, BUILDING REVIEW |
| | CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- CONTRACTOR'S LICENSE U-18134 SHOWN ON THE PERMIT |
| | APPLICATION IS FOR ROOFING CONTRACTOR. NEED TO PROVIDE |
| | CURRENT GENERAL/BUILDING OR RESIDENTIAL CONTRACTOR |
| | LICENSE TO DO THE WORK . |
| | |
| | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) GARAGE AND UTILITY ROOM EXTERIOR SWING DOORS. |
| | DRAWINGS SUBMITTED ARE FOR 8'-0" HIGH DOORS. NEED TO |
| | PROVIDE DRAWINGS FOR 6'-8" HIGH DOORS. SEE PLANS. |
| | |
| | B) ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | C) SLIDING GLASS DOORS WITH SIZE OF DOORS SPECIFIED ON |
| | PLANS. |
| | |
| | D) SINGLE HUNG IMPACT WINDOWS. IF USING IMPACT WINDOWS. |
| | PERMIT APPLICATION CALLS FOR IMPACT WINDOWS. PRODUCT |
| | APPROVAL SUBMITTED IS FOR NON IMPACT WINDOWS. |
| | |
| | E) STORM SHUTTERS IF NOT ISSUING IMPACT WINDOWS. AND |
| | PROVIDE COMPLETE INSTALLATION SCHEDULE. |
| | ***NOTE: SHUTERS INSTALLATION REQUIRES HISTORIC |
| | APPROVAL BEFORE SUBMITTING TO THIS OFFICE. |
| | |
| | 3- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 4- DOOR LEADING TO THE KITCHEN FROM THE GARAGE NEEDS TO |
| | BE FIRE RATED AS REQUIRED BY SEC. R309.1 OF 2007 |
| | FLORIDA RESIDENTIAL CODE. PROVIDE SPECIFICATIONS ON |
| | PLANS FOR TYPE OF DOOR TO BE INSTALLED. |
| | |
| | 5- NEED TO SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS |
| | REQUIRED BY SEC. R313.4 OF 2007 FLORIDA RESIDENTIAL |
| | CODE. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |