| Notes |
| Date |
Text |
| 2010-11-12 13:33:26 | PERMIT #10100237 | | | REVIEW COMMENTS - FIRE | | | | | | | | | FIRE AND LIFE SAFETY REQUIREMENTS TO CONFORM TO THE | | | FLORIDA FIRE PREVENTION CODE 2007 EDITION. | | | | | | ALL DEMOLITION WORK SHALL CONFORM TO THE REQUIREMENTS | | | OF NFPA 241. | | | | | | SMOKE ALARM INSTALLATION TO CONFORM TO THE REQUIREMENTS | | | OF NFPA 72. | | | | | | FIRE EXTINGUISHERS SHALL BE SERVICED AND TAGGED BY A | | | LICENSED FIRE EXTINGUISHER COMPANY. | | | | | | CARBON MONOXIDE ALARMS REQUIRED TO BE INSTALLED WITHIN | | | 10 FEET OF SLEEPING ROOMS FOR APARTMENTS UTILIZING GAS | | | RANGES OR GAS WATER HEATERS (FS553.885). | | | | | | MANY OF THE NEW BATHROOM DOORS HAVE A DOOR SWING THAT | | | OBSTRUCTS MORE THAN 50 PERCENT OF THE EGRESS PATH FOR | | | THE OCCUPANTS IN ADJACENT BEDROOMS (FFPC: NFPA 101 | | | SECTION 7.2.1.4.4). | | | | | | STAIRS EXCEEDING 30-INCHES ABOVE THE GROUND REQUIRE | | | GUARDS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|