| Notes |
| Date |
Text |
| 2010-12-08 14:54:59 | CLOTHES WASHERS APPEAR TO BE LOCATED WITHIN THE SAFE | | | WORKING ACCESS TO THE EXISTING ELECTRICAL PANELBOARDS. | | | NEC 110-26 | | | VERIFY THE EXISTING ELECTRICAL SERVICE , FEEDERS, | | | DISCONNECTS , AND GROUNDING SYSTEM ARE SUITABLE FOR | | | REUSE. NEC 230.2, 230.23, 230.42, 230.71, 250.20, | | | 250.53, 250.66 | | | HEATING OR COOLING LOADS HAVE NOT BEEN APPLIED TO THE | | | EXISTING ELECTRICAL CAPACITY. WILL HEATING OR COOLING | | | BE UTILIZED WITHIN THESE DWELLINGS? NEC 230-23 | | | | | | R. LECKY, PLANS EXAMINER, 561-805-6718 |
|