Notes
Date Text
2010-12-08 14:54:59CLOTHES WASHERS APPEAR TO BE LOCATED WITHIN THE SAFE
 WORKING ACCESS TO THE EXISTING ELECTRICAL PANELBOARDS.
 NEC 110-26
 VERIFY THE EXISTING ELECTRICAL SERVICE , FEEDERS,
 DISCONNECTS , AND GROUNDING SYSTEM ARE SUITABLE FOR
 REUSE. NEC 230.2, 230.23, 230.42, 230.71, 250.20,
 250.53, 250.66
 HEATING OR COOLING LOADS HAVE NOT BEEN APPLIED TO THE
 EXISTING ELECTRICAL CAPACITY. WILL HEATING OR COOLING
 BE UTILIZED WITHIN THESE DWELLINGS? NEC 230-23
  
 R. LECKY, PLANS EXAMINER, 561-805-6718