Plan Review Notes
Plan Review Notes For Permit 10100224
Permit Number 10100224
Review Stop B
Sequence Number 3
Notes
Date Text
2011-05-06 16:18:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PLEASE EXPLAIN HOW THE PROPOSED GABLE END BRACING
 DETAIL WILL RESIST NEGATIVE WIND PRESSURES, SHEET SK-1.
 THE BRACING DETAIL DOES NOT EXTEND TO THE GABLE END
 WALL, BUT APPEARS TO PROVIDE BRACING AT THE 2ND AND 3RD
 TRUSSES. BLOCKING IS SHOWN AT THE TOP, NONE SHOWN
 GRAPHICALLY AT THE BOTTOM BUT IS REFERRED TO AS
 EXISTING. IT IS NOT CLEAR HOW (OR WHETHER) THE 2X4 TOP
 AND BOTTOM BLOCKING WILL PROVIDE CONTINUITY TO THE
 PROPOSED X BRACE BETWEEN THE 2ND AND 3RD TRUSSES IN
 ORDER TO RESIST SUCTION PRESSURES. NOTE THAT THE
 TPI/WTCA BCSI 1-06 (PRODUCED JOINTLY BY THE WOOD TRUSS
 COUNCIL OF AMERICA AND TRUSS PLATE INSTITUTE) DETAIL
 EXTENDS FROM GABLE END WALL BACK 8' (FOUR TRUSSES).
 PLEASE REVISE DETAIL OR PROVIDE INFORMATION TO SHOW HOW
 THIS INFORMATION WILL RESIST NEGATIVE PRESSURES.
  
 2. TRUSS REPAIR DETAIL, SHEET SK-2, PLEASE SPECIFY
 TRUSS PLATE. STRUCTURAL COMPONENTS TO HAVE FLORIDA
 STATE OR LOCAL PRODUCT APPROVAL, FAC9N-3.
  
 3. THE CERTIFICATE OF AUTHORIZATION FOR THE ENGINEERING
 COMPANY, WARREN J. VON WERNE, PE, INC. IS NULL AND
 VOID. PLEASE EITHER REMOVE FROM TITLE BLOCK OR ACTIVATE
 THE COFA WITH FBPE, FS471, FAC61G15-23.002. ALSO PLEASE
 INCLUDE THE PRINTED NAME OF THE INDIVIDUAL WHO IS
 SEALING THE PLAN SO THE TITLE BLOCK WILL BE IN
 ACCORDANCE WITH FS471.
  
 4. PLEASE REVISE PLANS TO INCLUDE WIND DESIGN CRITERIA,
 FBC1603.1.4.
  
  
  