| Notes |
| Date |
Text |
| 2010-11-02 09:37:58 | PLAN DENIED | | | 1) PLEAS REFER TO SECTION 402 2007 FMC NATURAL | | | VENTILATION ( WINDOWS ON THE BUILBING ARE FIXED THEY DO | | | NOT OPEN ) PLEASE PROVIDE FRESH AIR CALCULATIONS ON THE | | | PLANS. | | | 2) REFER TO SECTION 606.3 2007 FMC INSTALLATION . | | | 3) WALK IN COOLERS AND KITCHEN HOOD REQUIRE THERE OWN | | | PLANS AND PERMITS. | | | 4) PLEASE PROVIDE A DETAIL ON THE PLAN FOR A/C CURB TO | | | ROOF TIE DOWN . | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|