2010-11-22 13:36:47RESIDENTIAL (R3) SCREEN ENCLOSURE, BUILDING REVIEW
 CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- MISSING FLOOR PLAN SHOWING LOCATION OF SCREEN
 ENCLOSURE. SEC. 106.1.1 AND SEC. 106.1.2 CITY
 AMENDMENTS TO FBC.
 AND, CLEARLY IDENTIFY EACH POST.
  
 2- PROVIDE COMPLETE SPECIFICATIONS AND DETAILS FOR
 CONCRETE SLAB AND FOOTING SIZES. SEC. 106.1.1 AND SEC.
 106.1.2 CITY AMENDMENTS TO FBC.
 AND, CLEARLY IDENTIFY EACH POST.
  
 3- REVISE DESIGN PARAMETERS:
 A) ACCORDING TO 2009 REVISIONS SEC. 1609.4.3 (SEC.
 R301.2.1.4.3 2007 FLORIDA RESIDENTIAL CODE) THIS
 BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". NEED TO
 REVISE THE DESIGN PARAMETERS FROM TABLE 2002.4 FOR
 EXPOSURE C.
  
 B) UPDATE ASCE 7 SPECIFIED ON DESIGN PARAMETERS. ASCE
 7-05 IS THE ONE THAT WAS ADOPTED BY THE FBC 2007. NOT
 ASCE 7-02. REVISE AS REQUIRED.
  
 4- A) REVISE ALL THE BEAMS AND COLUMNS TABLES TO VALUES
 THAT CORRESPOND TO EXPOSURE "C".
  
 B) NEED TO USE TABLES FOR BEAMS AND COLUMNS THAT TAKE
 INTO CONSIDERATION THE SOLID ALUMINUM ROOF PANELS.
 TABLES PROVIDED ARE NOT ADEQUATE FOR ROOF WITH SOLID
 PANELS.
  
 C) SPECIFY WHERE ARE THE BEAMS AND COLUMNS TABLES TAKEN
 FROM.
  
 5- CLARIFY IF THE ROOF PANELS ARE GOING TO HAVE
 OVERHANG OR NOT. DRAWINGS SUBMITTED DON'T SPECIFY ANY
 OVERHANG.
  
 6- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 DCA RULE 9B-72 FOR THE ALUMINUM ROOF PANELS TO BE USED.
  
 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) THE ALUMINUM ROOF PANEL
 PRODUCT APPROVAL PRIOR TO SUBMITTAL TO THIS OFFICE.
 SEC. 106.3.3 CITY AMENDMENTS TO FBC.
  
 8- PROVIDE ONLY THE DETAILS THAT APPLY TO THIS PROJECT.
 SPECIFY LOCATION OF "K" BRACING ON ELEVATIONS. SEE
 DETAIL. AND, PROVIDE ONLY THE TABLES THAT APPLY TO THIS
 PROJECT. SEC. 106.1.1.
  
 9- PROVIDE DETAIL CONNECTION TO THE EXISTING RESIDENCE.
 TOP VIEW FLOOR PLAN SPECIFIES 3" HEADER CHANNEL. THERE
 ARE NO DETAILS SHOWING THIS CONNECTION. SEC. 106.1.1.
  
 10. FRONT ELEVATION SPECIFIES 2X6 CARRIER BEAM. THIS
 DOESN'T CORRESPOND TO CARRY BEAM TABLE PROVIDED. REVISE
 AS REQUIRED AND COORDINATE WITH ITEM #4B ABOVE.
  
 11- PROVIDE TABLE THAT REFLECTS SIZE OF POSTS SPECIFIED
 ON ELEVATIONS TO VERIFY ALL LOADS AND SPACING.
 COORDINATE WITH ITEM #4B ABOVE. SEC. 106.1.1.
  
 12- PROVIDE COMPLETE DOOR FRAMING DETAILS. SPECIFY ALL
 FRAMING MEMBERS. SEC. 106.1.1
  
 13- REVISE COLUMN ANCHORING DETAIL. REVISE SIZE OF
 COLUMN TO MATCH SIZE SHOWN ON ELEVATIONS. ALSO, PROVIDE
 DETAIL FOR CORNER POSTS.
  
 14- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 ATTACHMENT OF ALUMINUM ROOF PANELS. DETAILS PROVIDED
 DON'T APPLY TO PROPOSED SCREEN ENCLOSURE. COORDINATE
 WITH PRODUCT APPROVAL SUBMITTED.
  
 15- PROVIDE COMPLETE DETAILS AND SPECIFICATIONS FOR
 COLUMN TO CARRIER BEAM CONNECTION, INCLUDING
 CONNECTIONS AT THE ENDS OF THE BEAM. SEC. 106.1.1.
  
 16- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. VALUATION WAS UPDATED TO INCLUDE ALL LABOR,
 MATERIALS AND ENGINEERING FEES. OWES $208.34.
  
 17- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTE.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 JULIO GOMEZ