| Plan Review Notes For Permit 10100163 |
| Permit Number |
10100163 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-29 14:40:45 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | FBC FLORIDA BUILDING CODE 2007 | | | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL | | | | | | 1. SEE FBC R CHAPTER 10; R1003, MASONRY CHIMNEYS AND | | | FBC R1005, FACTORY BUILT CHIMNEYS, AND FBC R 1801.3.4. | | | REVISE PLAN TO SHOW COMPLIANCE AND PROVIDE ANY | | | ADDITIONAL SUPPLEMENTARY INFORMATION REQUIRED TO SHOW | | | COMPLIANCE. PROVIDE A COMPLETE DETAIL OF THE CHIMNEY, | | | ALL COMPONENTS AFFECTED. | | | | | | 2. SHOW DISTANCE FROM ROOF TO TOP OF CHIMNEY, FBC R CH. | | | 10, 18. | | | | | | 3. PLANS ARE TITLED "REMODEL ADDITION." ON THE PLAN, | | | PLEASE INDICATE REPAIR AREAS AND NEW. ALSO NOTE IF THE | | | NEW AREAS ARE UNDER AIR OR COVERED PORCH AREAS (IMPACT | | | FEES MAY BE REQUIRED). | | | | | | 4. APPLICATION STATES THAT CLERESTORY WINDOWS WILL BE | | | INSTALLED. BOTH FIXED WINDOWS AND CASEMENT WINDOW | | | PRODUCT APPROVAL SUBMITTED. PLAN DOES NOT SHOW ANY | | | WINDOW INSTALLATION. PROVIDE A FLOOR PLAN SHOWING | | | WINDOW LOCATIONS, SIZES. WILL THE CASEMENT WINDOW BE | | | INSTALLED IN THE CLERESTORY OR ARE YOU REPLACING | | | EXISTING WINDOWS IN OTHER AREAS OF THE HOUSE? FBC*106, | | | FBC R301. | | | | | | 5. FOR THE FLAT DECK ROOF, SPECIFY ENHANCED FASTENING | | | FOR ZONES 2 AND 3, FBC R301. |
|