| 2010-10-08 17:22:59 | **PROVISO** | | | | | | 1. PG M0.1: CORRECT MATHEMATICAL ERROR IN VENTILATION | | | CALCULATIONS. SEE DRAWING MARK-UP. | | | | | | 2. PG M0.1: CALCULATE CONFERENCE ROOMS, LOBBIES AND | | | BREAKROOMS SEPARATELY FROM GENERAL OFFICE SPACE PER | | | AHSRAE 62.1-2004 TABLE 6-1. | | | | | | 3. PG M0.2: FIRE DAMPER INSTALLATION SHALL BE IN | | | ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS PER FBC-M | | | 607.2. | | | | | | 4. PG M2.2: ARCHITECTURAL PLANS SHOW FULL HEIGHT | | | PARTITIONS SEPARATING LOBBY 200, CONFERENCE 201 AND | | | CONFERENCE 202 FROM THE REMAINDER OF THE CONDITIONED | | | SPACES. SHOW HOW BALANCED RETURN IS TO BE ACHIEVED IN | | | THIS AREA PER FBC-M 601.4. | | | | | | |
|