| 2010-10-25 13:35:29 | BUILDING PLAN REVIEW |
| | PERMIT: 10100153 |
| | ADD: 321 8TH ST |
| | CONT: BELLA CONSTRUCTION |
| | TEL: (561)722-6402 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | REVIEW: DENIED |
| | |
| | 1) SITE PLAN REVIEW: |
| | |
| | 1A) THE FRONT ENTRY IS NOT THE ACCESSIBLE ENTRY, |
| | 11-4.1.8(3) DOES ALLOW FOR ALTERNATE ENTRY PLEASE |
| | INDICATE HOW COMPLIANCE WITH THE ARCHITECTURAL BARRIER |
| | REMOVAL ACT WOULD NOT BE READILY ACHIEVABLE. IN BOTH |
| | CASES FRONT OR REAR ENTRY THE ENTRANCE WOULD NEED TO BE |
| | MODIFIED BY CHANGE OF ELEVATION. |
| | |
| | 1B) FOR ENTRANCES THAT ARE NOT ACCESSIBLE PLEASE REVIEW |
| | REQUIRED SIGNAGE 11-4.1.8(3) , 11-4.30.1. & 11-4.30.7. |
| | |
| | 1C) THE REAR OF THE BUILDING INDICATES THE ACCESSIBLE |
| | PATH WITH THE USE OF A RAMP FOR CHANGE IN ELEVATION. |
| | PLEASE REVIEW SECTION 11-4.8.4(2) FOR THE REQUIRED |
| | LENGTH OF THE BOTTOM LANDING. ALL LANDINGS ON RAMPS |
| | SHALL NOT BE LESS THAN 60" CLEAR, & THE BOTTOM OF EACH |
| | RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT & LEVEL |
| | CLEARANCE. |
| | |
| | 1D) THE OTHER ISSUE WITH THE RAMP IS THE MID LANDING |
| | AND CHANGE OF DIRECTION. 11-4.8.4(3) IF RAMPS CHANGE |
| | DIRECTION AT LANDINGS, THE MINIMUM LANDING SIZE SHALL |
| | BE 60" X 60". |
| | |
| | 1E) PLANS INDICATE THIS TO BE A LEVEL III ALTERATION |
| | BUT IS IT A CHANGE OF OCCUPANCY FROMR-3 TO BUSINESS? IF |
| | SO PALM BEACH COUNTY IMPACT FEE OFFICE WILL NEED TO |
| | REVIEW PLANS FOR ASSESSMENT. |
| | |
| | 2) THE FRONT ENTRY DOORS ARE LACKING PRODUCT APPROVALS |
| | AS PER RULE 9B-72(31)(A) FOR EXTERIOR DOORS. SHEET S-1 |
| | INDICATES IN SECTION #1 INDICATES THE DOORS TO BE |
| | WITHIN A DOOR FRAME AND TRANSOM TO BE IMPOSED UPON THE |
| | BEAM MORE OF A MOCK TRANSOM? |
| | |
| | 3) ADDITIONAL INFORMATION REQUIRED 106.1.2 SHEET A-300 |
| | INDICATES THE USE OF CAST STONE TRIM PLEASE PROVIDE |
| | COMPLIANCE WITH EITHER FBC-B 1405.6, 1405.7 OR 1405.9. |
| | |
| | 4) A-3 AND STRUCTURAL SHEETS ALSO INDICATE A NEW |
| | CRICKET BUT THE PLANS INDICATE THE TYPE OF ROOF |
| | COVERING TO BE SHINGLES. NO ROOFING PRODUCT APPROVALS |
| | SUBMITTED, RULE 9B-72(31)(D) WILL REQUIRE PRODUCT |
| | APPROVALS AT TIME OF THE ROOFING PERMIT IS APPLIED FOR. |
| | |
| | 5) SHEET M-1 IT APPEARS THAT THE A/C CONDENSERS ARE TO |
| | BE ROOF MOUNTED, IF THIS IS THE CASE RULE 9-B-72(31)(G) |
| | REQUIRES PRODUCT APPROVALS FOR PRE-ENGINEERED AIR |
| | CONDITIONING STANDS. THE SITE PLANS DO INDICATE |
| | EXISTING CONCRETE A/C PAD? |
| | |
| | 6) A-400 INDICATES THE USE OF ICYNENE FOAM INSULATION |
| | PLEASE PROVIDE PRODUCT TESTING REPORTS AS TO |
| | LIMITATIONS. FBC-B 2603.4. |
| | |
| | JIM WITMER C. B. O. |
| | COMMERCIAL COMBINATION PLAN REVIEW |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | PLEASE TAKE A MOMENT TO COMPLETE OUR ANONYMOUS ON-LINE |
| | CUSTOMER SERVICE SURVEY AT: |
| | WWW.SURVEYMONKEY.COM/WESTPALMBEACHCONSTRUCTIONSERVICES |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |