2010-11-17 10:25:532007 FBC W/2009 REVISIONS
  
 DENIED BY PLUMBING
  
 1) SUBMIT 2 COPIES OF SPECIFICATIONS FOR EACH OF THE
 PUMPS THAT WILL BE INSTALLED. INCLUDE THE PUMP CURVES
 FOR THE PUMPS.
  
 2) SUBMIT 2 COPIES OF TOTAL DYNAMIC HEAD (TDH)
 CALCULATIONS FROM THE DESIGNER OF RECORD FOR EACH OF
 THE PUMPS. OTHERWISE THE MAXIMUM PUMP CAPACITY IN GPM
 WILL BE USED TO DETERMINE THE FLOW RATE.
  
 3) UNDER AUX. POOL SPECS ON DRAWING 1, A SHARED 2.0 HP
 PUMP IS SPECIFIED. THE REST OF THE PLANS SPECIFY A
 1-1/2 HP PUMP FOR THE POOL AND A 1-1/2 HP PUMP FOR THE
 VANISHING EDGE. PLEASE CLARIFY.
  
 4) THE VANISHING EDGE DETAIL ON DRAWING 3 SPECIFIES TWO
 8" DRAINS AND THE OTHER DRAWINGS SHOW A CHANNEL DRAIN.
 PLEASE CORRECT.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW