| Plan Review Notes For Permit 10100040 |
| Permit Number |
10100040 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-29 09:48:35 | ****PROVISO**** | | | ****REVISION REQUIRED**** | | | | | | 1. REVISE EXPOSURE CATEGORY OR EXPLAIN RATIONALE FOR | | | EXPOSURE B. FBC1609, FBC R301.2.1.4. NOTE THAT THE CODE | | | CHANGED EFFECTIVE MARCH 1, 2009. | | | | | | R301.2.1.4 EXPOSURE CATEGORY. FOR EACH WIND DIRECTION | | | CONSIDERED, AN EXPOSURE CATEGORY THAT ADEQUATELY | | | REFLECTS THE CHARACTERISTICS OF GROUND SURFACE | | | IRREGULARITIES SHALL BE DETERMINED FOR THE SITE AT | | | WHICH THE BUILDING OR STRUCTURE IS TO BE CONSTRUCTED. | | | FOR A SITE LOCATED IN THE TRANSITION ZONE BETWEEN | | | CATEGORIES, THE CATEGORY RESULTING IN THE LARGEST WIND | | | FORCES SHALL APPLY. ACCOUNT SHALL BE TAKEN OF | | | VARIATIONS IN GROUND SURFACE ROUGHNESS THAT ARISE FROM | | | NATURAL TOPOGRAPHY AND VEGETATION AS WELL AS FROM | | | CONSTRUCTED FEATURES. FOR ANY GIVEN WIND DIRECTION, THE | | | EXPOSURE IN WHICH A SPECIFIC BUILDING OR OTHER | | | STRUCTURE IS SITED SHALL BE ASSESSED AS BEING ONE OF | | | THE FOLLOWING CATEGORIES: | | | | | | EXCEPTION: AN INTERMEDIATE EXPOSURE BETWEEN THE | | | EXPOSURE CATEGORIES DEFINED IS PERMITTED IN A | | | TRANSITION ZONE PROVIDED THAT IT IS DETERMINED BY A | | | RATIONAL ANALYSIS METHOD. | | | | | | EITHER SUBMIT PLANS DESIGNED TO EXPOSURE C OR PROVIDE | | | ANALYSIS FOR EXPOSURE C. | | | | | | | | | |
|