| 2010-10-21 15:55:09 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) THE PLANS SPECIFY EXPOSURE CATEGORY B. BASED ON FBC |
| | R301.2.1.4.3 THE STRUCTURE IS LOCATED IN EXPOSURE |
| | CATEGORY C. PLEASE REVISE THE PLANS. THIS WILL ALSO |
| | RESULT IN AN INCREASE IN THE COMPONENT AND CLADDING |
| | PRESSURES. PLEASE REVISE THESE ALSO. |
| | |
| | 2) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND LISTING INFORMATION FOR THE PRE-FAB |
| | FIREPLACE, CHIMNEY AND CHIMNEY CAP. |
| | |
| | 3) SUBMIT TWO COPIES OF THE MANUFACTURER'S |
| | SPECIFICATIONS AND LISTING INFORMATION FOR THE GAS BBQ |
| | GRILL AT THE COVERED PORCH. |
| | |
| | 4) PROVIDE DETAILS FOR THE 36" EXTERIOR FIREPLACE |
| | LOCATED ON THE COVERED PORCH. IS THIS A MASONRY |
| | FIREPLACE? PLEASE CLARIFY. |
| | |
| | 5) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED FOR |
| | THE CONCRETE ROOF TILES BY CIRCLING THE METHOD AND |
| | MOMENT OF RESISTANCE FROM THE TABLES LISTED IN THE |
| | TILE'S PRODUCT APPROVAL. |
| | |
| | 6) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE |
| | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE |
| | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF |
| | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 7) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE TRUSS |
| | CONNECTORS THAT WILL BE USED AS REQUIRED BY DCA RULE |
| | 9B-72. |
| | |
| | 8) THE DESIGN PRESSURES FOR THE 2" X HEAVY WALL TUBE |
| | MULLIONS IN THE PRODUCT APPROVALS SUBMITTED ARE TOO LOW |
| | FOR USE BETWEEN THE 12 FT WIDE SLIDING GLASS DOORS AND |
| | THE TRANSOM WINDOWS ABOVE THEM. PLEASE CORRECT. |
| | |
| | 9) THE PRODUCT APPROVALS FOR THE PGT FD-750 OUTSWING |
| | ALUMINUM FRENCH DOOR IS EXPIRED. SUBMIT THE CURRENT |
| | NOAS (09-1028.10). |
| | |
| | 10) THE PRODUCT APPROVALS FOR THE 9' WIDE AND 16' WIDE |
| | AMARR GARAGE DOORS HAVE BEEN SUPERSEDED. SUBMIT THE |
| | CURRENT NOAS (09-0604.03/09-0604.05). |
| | |
| | 11) THE PRODUCT APPROVALS FOR THE PGT PW-701 FIXED |
| | WINDOW HAVE BEEN SUPERSEDED. SUBMIT THE CURRENT NOA |
| | (10-0504.05) |
| | |