| Plan Review Notes For Permit 10090847 |
| Permit Number |
10090847 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-10-13 12:26:58 | 1217 SOUTH FLAGLER DRIVE | | | PERMIT NUMBER 10090847 | | | 'REPLACEMENT OF SPRINKLER UNDER BUILDING - PARKING | | | FACILITY" | | | | | | | | | 1. ON OCTOBER 13, 2010, THIS WRITER CONTACTED ROY ZIEK | | | OF JOHN W. POLHEMUS BY TELEPHONE. WE DISCUSSED IF AN | | | EXISTING FIRE DEPARTMENT CONNECTION (FDC) IS AVAILABLE. | | | MR. ZIEK IS TO VERIFY EXISTING FIRE DEPARTMENT | | | CONNECTION. | | | | | | 2. THE EXISTING FIRE DEPARTMENT CONNECTION SHOULD | | | INSPECTED TO DETERMINE IF IT IS OPERATIONAL, EQUIPPED | | | WITH CAPS, AND DO THE HOSE CONNECTIONS SWIVEL. | | | | | | 3. THE WORK DISPLAYED ON THE PLANS IS A LIKE FOR LIKE | | | REPLACEMENT EXCEPT FOR CORROSION RESISTANT PIPING AND | | | FIRE SPRINKLER HEADS. | | | | | | 4. THE NEW FIRE SPRINKLER PIPING IS TO BE PRESSURE | | | TESTED AT 200 PSI FOR 2 HOURS AND WITNESSED BY THIS | | | OFFICE. | | | | | | 5. INSTALLATION SHALL BE IN ACCORDANCE WITH NFPA 13, | | | 2002 EDITION. | | | | | | 6. THE FIRE SPRINKLER SYSTEM SHALL BE INSPECTED AND | | | APPROVED BY THIS OFFICE AFTER INSTALLATION. | | | | | | APPROVED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|