| 2010-10-29 11:51:37 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PROVIDE A COMPLETE DETAIL FOR PROPOSED CONSTRUCTION. |
| | FOR INSTANCE, CROSS BRACING SHOWN WELDED TO BEAM AND |
| | POST WITH NO SPEC FOR WELD AND NO SPECIFICATION FOR |
| | MATERIAL OR DIMENSIONS FOR ATTACHMENT LOCATION. NO |
| | CATWALK INFORMATION PROVIDED. |
| | |
| | 2. W5X16 BEAM SHOWN, WELDED TO AN UNMARKED BRACE, |
| | WELDED TO ALUMINUM POST. PLEASE PROVIDE COMPLETE |
| | INFORMATION. CALCULATIONS MAY BE REQUIRED. |
| | |
| | 3. PROVIDE DIMENSIONS FOR STAIRS, FBC R 311.5.3, |
| | 311.5.8. TREAD INFORMATION NOT PROVIDED. |
| | |
| | 4. SHOW HEADROOM BETWEEN TREAD AND BOTTOM OF CATWALK, |
| | WORSE CASE, FBC R311.5.2. |
| | |
| | 4. FOOTER DETAIL STATES "CONCRETE FOOTER OR BEAR ON CAP |
| | ROCK." SPECIFICATION IS INCOMPLETE. CONCRETE FOOTER IS |
| | SHOWN 16"X12", WHAT SIZE CAP ROCK WOULD BE SUFFICIENT? |
| | IS THE FOOTER ROUND OR SQUARE? |
| | |
| | 5. PLANS ARE REQUIRED TO SCALE, FBC106. DETAILS ARE |
| | MARKED "NTS." |
| | |
| | 6. TERMINATION OF CATWALK IS NOT CLEAR. DOES THIS |
| | TERMINATE AT A CANTALEVERED BALCONY? FBC R311.2.1. |
| | |
| | 7. CATWALK IS SHOWN AS 120" ON ONE DRAWING, 6' ON |
| | ANOTHER DETAIL. PROVIDE DRAWINGS, TO SCALE, WHICH |
| | CLEARLY DEPICT SCOPE OF WORK. |
| | |
| | 8. 4 WOOD SCREWS ARE SHOWN AT THE BALCONY. IT IS NOT |
| | CLEAR WHAT THIS IS FOR, SIZE OF SCREWS REQUIRED, IS |
| | THIS EXISTING OR PROPOSED CONSTRUCTION? |
| | |
| | 9. ENGINEERED SHOP DRAWINGS REVIEWED BY DESIGNER OF |
| | RECORD WILL BE REQUIRED, FBC TABLE R301.5. |
| | |
| | |
| | |
| | |
| | |