Plan Review Notes
Plan Review Notes For Permit 10090800
Permit Number 10090800
Review Stop B
Sequence Number 1
Notes
Date Text
2010-10-29 11:51:37****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A COMPLETE DETAIL FOR PROPOSED CONSTRUCTION.
 FOR INSTANCE, CROSS BRACING SHOWN WELDED TO BEAM AND
 POST WITH NO SPEC FOR WELD AND NO SPECIFICATION FOR
 MATERIAL OR DIMENSIONS FOR ATTACHMENT LOCATION. NO
 CATWALK INFORMATION PROVIDED.
  
 2. W5X16 BEAM SHOWN, WELDED TO AN UNMARKED BRACE,
 WELDED TO ALUMINUM POST. PLEASE PROVIDE COMPLETE
 INFORMATION. CALCULATIONS MAY BE REQUIRED.
  
 3. PROVIDE DIMENSIONS FOR STAIRS, FBC R 311.5.3,
 311.5.8. TREAD INFORMATION NOT PROVIDED.
  
 4. SHOW HEADROOM BETWEEN TREAD AND BOTTOM OF CATWALK,
 WORSE CASE, FBC R311.5.2.
  
 4. FOOTER DETAIL STATES "CONCRETE FOOTER OR BEAR ON CAP
 ROCK." SPECIFICATION IS INCOMPLETE. CONCRETE FOOTER IS
 SHOWN 16"X12", WHAT SIZE CAP ROCK WOULD BE SUFFICIENT?
 IS THE FOOTER ROUND OR SQUARE?
  
 5. PLANS ARE REQUIRED TO SCALE, FBC106. DETAILS ARE
 MARKED "NTS."
  
 6. TERMINATION OF CATWALK IS NOT CLEAR. DOES THIS
 TERMINATE AT A CANTALEVERED BALCONY? FBC R311.2.1.
  
 7. CATWALK IS SHOWN AS 120" ON ONE DRAWING, 6' ON
 ANOTHER DETAIL. PROVIDE DRAWINGS, TO SCALE, WHICH
 CLEARLY DEPICT SCOPE OF WORK.
  
 8. 4 WOOD SCREWS ARE SHOWN AT THE BALCONY. IT IS NOT
 CLEAR WHAT THIS IS FOR, SIZE OF SCREWS REQUIRED, IS
 THIS EXISTING OR PROPOSED CONSTRUCTION?
  
 9. ENGINEERED SHOP DRAWINGS REVIEWED BY DESIGNER OF
 RECORD WILL BE REQUIRED, FBC TABLE R301.5.
  
  
  
  
  