Plan Review Notes
Plan Review Notes For Permit 10090790
Permit Number 10090790
Review Stop B
Sequence Number 1
Notes
Date Text
2010-09-29 09:37:32RESIDENTIAL (R3) RE-ROOF, BUILDING REVIEW CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE SIGNED AND SEALED RAS 117 CALCULATIONS (2
 COPIES) FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA 07-1219.09.
  
 2- DESIGN PROFESSIONAL DOING THE RAS 117 CALCULATIONS
 TO TAKE INTO CONSIDERATION THAT ACCORDING TO 2009
 REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON
 EXPOSURE "C".
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712
  
  