| Plan Review Notes For Permit 10090787 |
| Permit Number |
10090787 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-09-30 16:21:00 | 600 VILLAGE BOULEVARD | | | PERMIT #10090787 | | | MASTER #10070434 | | | | | | 1) UPDATE FLOOR PLAN AND SPRINKLER COVERAGE FOR REVISED | | | (EXPANDED) PATIO. | | | | | | 2) PROVIDE HYDRAULIC CALCULATIONS ACCOUNTING FOR | | | FRICTION LOSS IN FLEXIBLE DROPS AND SYSTEM EXTENSION. | | | PROVIDE UPDATED HYDRAULIC PLACARD DATA ON PLAN. | | | | | | 3) PROVIDE VERIFICATION THAT THE AWNING STRUCTURE WILL | | | SUPPORT THE LOAD OF WATER-FILLED SPRINKLER PIPING. | | | | | | 4) PROVIDE ADDITIONAL FLEXHEAD INFORMATION STATING | | | MAXIMUM NUMBER OF BENDS PERMITTED AND MINIMUM RADIUS | | | REQUIRED PER THE LISTING REQUIREMENTS. | | | | | | 5) PROVIDE CURRENT HYDRANT FLOW TEST DATA. | | | | | | 6) PROVIDE LOCKABLE KNOX CAPS ON EXISTING FIRE | | | DEPARTMENT CONNECTION. | | | | | | 7) FOR AREAS EXPOSED TO STRUCTURE, PROVIDE THE | | | CONSTRUCTION TYPE (OBSTRUCTED/UNOBSTRUCTED) AND THE | | | SPRINKLER LOCATION IN REFERENCE TO DISTANCE BELOW THE | | | ROOF DECK. | | | | | | 8) EXISTING BRANCH LINE ROUTED THROUGH ELECTRICAL ROOM | | | TO BE RE-ROUTED OUTSIDE OF ELECTRICAL ROOM. ONLY THE | | | SPRINKLERS PROTECTING THE ELECTRICAL ROOM ARE PERMITTED | | | BY NFPA 70. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6730 |
|